5587001-YSG-A-520 | Start-Up & Operation Guide
Table 32: BACnet Points List (Continued)
BACnet
Object
Attributes
Type
OprOcc
MV
OccMode
MV
NetTempOcc
MV
NetOcc
MV
ZTSrc
MV
IAQSrc
MV
SHSrc
MV
OprFanReq
MV
FanReqSrc
MV
NetFanReq
MV
OATSrc
MV
108
Object
Read/
Short Description
ID
Write
29517
R
OprOcc
29518
R/W
OccMode
29519
R/W
NetTempOcc
29520
R/W
NetOcc
29523
R
ZTSrc
29528
R
IAQSrc
29532
R
SHSrc
29534
R
OprFanReq
29535
R
FanReqSrc
29536
R/W
NetFanReq
29542
R
OATSrc
Long
Point Definitions (Units)
Description
Displays the occupancy status of the
unit
Operational
0 = OCC
Occupancy
1 = UNOCC
2 = bypass
3 = standby
A BAS command that allows the unit
Occupancy Mode
to be placed in a occupancy mode
0 = schedule 1 = external
Network
A BAS command to request network
Temporary
temporary occupancy
Occupancy
0 = false 1 = true
Request
A BAS command to request network
Network
occupancy
Occupancy
0 = OCC
Request
1 = UNOCC
2 = not set
Displays the source of ZT input
0 = unreliable
ZT Source
1 = local input
2 = network sensor
3 = high priority
Displays the source of IAQ (CO
input
0 = unreliable
IAQ Source
1 = local input
2 = network sensor
3 = high priority
Displays the source of
space humidity input
Space Humidity
0 = unreliable
Source
1 = local input
2 = network sensor
3 = high priority
Operating Fan
Displays the status of supply fan
Request
request
Displays the source of supply fan
request input
Fan Request
0 = unreliable
Source
1 = local input
2 = network sensor
3 = high priority"
A BAS command that allows user to
Network Override
request for supply fan
Fan Request
0 = OFF 1 = ON
Displays the source of OAT input
0 = unreliable
OAT Source
1 = local input
2 = network sensor
3 = high priority
)
2
0 = OFF 1 = ON