York Sun Premier GZA1M Series Start-Up & Operation page 112

Rooftop units
Table of Contents

Advertisement

5587001-YSG-A-520 | Start-Up & Operation Guide
Table 32: BACnet Points List (Continued)
BACnet
Object
Attributes
Type
ExFan
MV
ExF-S
MV
ExFanVFDFlt
MV
ERV-En
MV
HGR-En
MV
HGR-S
MV
OprSafetyCmd
MV
SafetyCmdSrc
MV
Safety1
MV
NetSafety
MV
SS-S
MV
Unit-S
MV
ExcessOutAirFlt
MV
NotEconFlt
MV
EconDampFlt
MV
112
Object
Read/
Short Description
ID
Write
29775
R
EF-C
29777
R
ExRt-S
29778
R
ExFanVFDFlt
29787
R/W
ERV-En
29789
R/W
HGR-En
29791
R
HGR-S
29798
R
OprSafetyCmd
29799
R
SafetyCmdSrc
29800
R
Safety1
29801
R/W
NetSafety
29802
R
SS-S
29803
R
Unit-S
Not Displayed
29809
R
Locally
Not Displayed
29810
R
Locally
Not Displayed
29811
R
Locally
Long
Point Definitions (Units)
Description
Exhaust Fan
Displays the command of exhaust
Command
fan/return fan
Displays the status of exhaust/return
fan
Exhaust Return
0 = OFF/idle
Fan Status
1 = ON/normal command
2 = OFF/disabled
3 = OFF/VFD fault
Exhaust Fan VFD
Displays the status of the exhaust/
Fault
return fan fault 0 = normal 1 = alarm
A BAS command to enable ERW
ERV Enabled
0 = NO 1 = YES
A BAS command to enable HGRH
HGRH Enabled
0 = none
For Operation
1 = normal
2 = alternate
Displays the status of HGRH
0 = OFF/idle
HGRH Status
1 = ON/normal command
2 = ON/alternate operation command
3 = OFF/disabled
Displays the status of safety
command
Operating Safety
0 = normal
Command
1 = pressurize
2 = depressurize
3 = purge
Displays the source of safety
command input:
Safety Command
0 = unreliable
Source
1 = local input
2 = network sensor
3 = high priority
Local Safety
Displays the status of local safety
Command Input 1
command input 1
Network Override
A BAS command to override safety
Safety Command
command
Safety Switch
Displays the unit safety switch status
Status
0=normal 1=alarm
Displays the unit status
0 = idle
Unit Status
1 = SD alarm
2 = purge command
3 = start-up wizard
Not Displayed
Displays the excess outside air fault
Locally
0 = normal 1 = alarm
Displays the economizer not available
Not Displayed
for suitable outside air conditions
Locally
0 = normal 1 = alarm
Not Displayed
Displays the economizer damper fault
Locally
0=normal 1=alarm
0 = OFF 1 = ON
0 = false 1 = true
0 = false 1 = true
YORK