York Sun Premier GZA1M Series Start-Up & Operation page 71

Rooftop units
Table of Contents

Advertisement

Table 26: Menus and Submenus (Continued)
Menu
Submenu
Commissioning
Mode >
Air Handler
Commissioning
Mode >
Air Handler
Commission
(Figure 28)
Commissioning
Mode > Cooling
YORK
Parameters Displayed / Default
Commissioning Mode / Disable
Commissioning Time Remaining
Extend Commissioning Time / No
SF-C (Supply Fan Command) / OFF
SF-O (Fan % Command) / 0%
Supply Fan VFD 2
Econ (Economizer Damper %
Command) / 0%
EF-C (Exhaust Fan Command) / OFF
EF-O (Exhaust Fan VFD % Command)
Exhaust Fan VFD 2
Humidifier Command / OFF
Humidifier % Command / 0%
HREAFBD-C (Heat Recovery EA Face
Bypass Damper Command) / Close
HRW-C (Heat Recovery Wheel
Command) / OFF
HRW-O (Heat Recovery Wheel Output)
/ 0%
EAD-O (Exhaust Damper % Command)
/ 0%
FaultOut1 / OFF
FaultOut2 / OFF
IsoDmpr (Isolation Damper) / Close
VAV Box (MZVAV Box Heat Command)
/ OFF
Commissioning Mode / Disable
Commissioning Time Remaining
Extend Commissioning Time / No
SF-C (Supply Fan Command)
SF-O (Fan % Command) / 0%
C1A (Compressor 1A Command)
ModCompOut (Modulating Compressor
Output)
C1B (Compressor 1B Command) / OFF
C2A (Compressor 2A Command) / OFF
C2B (Compressor 2B Command) / OFF
CF-1A (Condenser Fan 1A) / OFF
ModCondFan1Out (Modulating
Condenser Fan 1 Output)
CF-1B (Condenser Fan 1B) / OFF
CF-2A (Condenser Fan 2A) / OFF
ModCondFan2Out (Modulating
Condenser Fan 2 Output)
CF-2B (Condenser Fan 2B) / OFF
HGR (Hot Gas Reheat Command) / 0%
Start-Up & Operation Guide | 5587001-YSG-A-520
Conditions for Parameters Displayed
Units / Range
Disable, Enable
minutes
No, Yes
OFF, ON
% (0–100)
OFF, ON
% (0–100)
OFF, ON
%
OFF, ON
OFF, ON
% (0–100)
Close, Open
OFF, ON
% (0–100)
% (0–100)
OFF, ON
OFF, ON
Close, Open
OFF, ON
Disable, Enable
minutes
No, Yes
OFF, ON
% (0–100)
OFF, ON
% (0–100)
OFF, ON
OFF, ON
OFF, ON
OFF, ON
% (0–100)
OFF, ON
OFF, ON
% (0–100)
OFF, ON
% (0–100)
71