Installation Manual: YORK Sun™ Select ® YV28 to YV50 York International Corporation, 5005 5759090-YIM-A-0320 York Drive, Norman, OK 73069 Revision: A-0320 www.york.com 2020-05-01 Johnson Controls Ducted Systems...
Drive selection............79 Constant volume medium static....40 Airflow performance........... 80 Constant volume high static......42 Air balance............. 81 VFD Two-stage standard static...... 44 Checking air quantity..........82 Installation Manual: YORK Sun™ Select YV28 to YV50 ® Johnson Controls Ducted Systems...
Page 4
Two Stage................ 91 Adjustment Of Temperature Rise........ 91 Burners/Orifices Inspection/Servicing......92 Charging tables..............93 Smart Equipment™ unit control board......96 Four-stage board............... 101 Cable recommendations..........103 Start-up sheet..............104 Installation Manual: YORK Sun™ Select YV28 to YV50 ® Johnson Controls Ducted Systems...
*When servicing controls, label all wires prior to including, but not limited to building, electrical, disconnecting. Reconnect wires correctly. and mechanical codes. *Verify proper operation after servicing. Installation Manual: YORK Sun™ Select YV28 to YV50 ® Johnson Controls Ducted Systems...
Untrained Renewal parts personnel can perform basic maintenance functions of cleaning coils and filters, and replacing filters. Contact your local York parts distribution center ® Observe all the precautions in the literature, labels, for authorized replacement parts.
Page 7
CAUTION This system uses R-410A refrigerant which operates at higher pressures than R-22. No other refrigerant may be used in this system. Installation Manual: YORK Sun™ Select YV28 to YV50 ® Johnson Controls Ducted Systems...
This may result in a fire or explosion, causing property damage, personal injury, or loss of life. Installation Manual: YORK Sun™ Select YV28 to YV50 ® Johnson Controls Ducted Systems...
Page 10
(such as computer rooms or switchgear), call the applications department for Ducted Systems at 1-877-874-SERV for guidance. Additional accessories may be needed for stable operation at temperatures below 30°F. Installation Manual: YORK Sun™ Select YV28 to YV50 ® Johnson Controls Ducted Systems...
Scroll compressors in various arrangements to produce Filter access, 2-in. or 4-in. filter options two stages or four stages of cooling, depending on the selected model Condenser fans Microchannel condenser coils Installation Manual: YORK Sun™ Select YV28 to YV50 ® Johnson Controls Ducted Systems...
Detailed unit clearances are available in the Weights and dimensions section. WARNING Do not permit overhanging structures or shrubs to obstruct the condenser air discharge outlet, combustion air inlet, or vent outlets. Installation Manual: YORK Sun™ Select YV28 to YV50 ® Johnson Controls Ducted Systems...
The spreader bars must have a length that exceeds the largest dimension across the unit. CAUTION If a unit is installed on a roof curb other than a YORK roof curb, you must apply gasketing to all surfaces that come in contact with the unit underside.
Weights and dimensions Figure 3: YV28 to YV35 physical dimensions Installation Manual: YORK Sun™ Select YV28 to YV50 ® Johnson Controls Ducted Systems...
Page 15
Figure 4: YV40 to YV50 physical dimensions Installation Manual: YORK Sun™ Select YV28 to YV50 ® Johnson Controls Ducted Systems...
To install the outdoor air hood, complete the following steps. While transporting the unit, the hood top panel is used as a shipping cover attached to the unit exterior as shown in Figure 7. Installation Manual: YORK Sun™ Select YV28 to YV50 ® Johnson Controls Ducted Systems...
Page 17
2, slide the flange under the lip at the top of the hood assembly. Lay the panel on top of the left side and right side panels. Installation Manual: YORK Sun™ Select YV28 to YV50 ® Johnson Controls Ducted Systems...
Figure 13: Filter support assembly the unit exterior as shown in Figure 15. Figure 15: Manual damper hood top panel Item Description Filter support Screws Item Description Hood top panel Installation Manual: YORK Sun™ Select YV28 to YV50 ® Johnson Controls Ducted Systems...
Page 19
Using three of the no. 10 screws that were removed in Step 2, attach the left side panel and right side panel to the unit as shown in Figure 18 and Figure 19. Installation Manual: YORK Sun™ Select YV28 to YV50 ® Johnson Controls Ducted Systems...
To install the exhaust hood, complete the following the remaining screws in the hardware bag as steps. shown in Figure 22. The completed assembly will resemble Figure 23. Installation Manual: YORK Sun™ Select YV28 to YV50 ® Johnson Controls Ducted Systems...
Page 21
See those instructions for location. Attach the hood top panel to the side panels using the screws removed in Step 2. The completed assembly will resemble Figure 28. Installation Manual: YORK Sun™ Select YV28 to YV50 ® Johnson Controls Ducted Systems...
DPS (identified in Step 1), down through the hole in the knock-out in the bottom of the control box, and to the desired location for obtaining the building pressure. Installation Manual: YORK Sun™ Select YV28 to YV50 ® Johnson Controls Ducted Systems...
Page 23
High pressure port the unit base, route the tubing to the desired Low Pressure port location for obtaining a constant building pressure reading. Figure 33: Routing the tubing Installation Manual: YORK Sun™ Select YV28 to YV50 ® Johnson Controls Ducted Systems...
The condensate drain connection is oriented for a through the side connection as shown in Figure 35. Item Description High SA duct pressure Low building pressure Supply air duct Installation Manual: YORK Sun™ Select YV28 to YV50 ® Johnson Controls Ducted Systems...
Page 25
Note: The trap and drain lines must be protected from freezing and the plumbing must conform to local codes. Figure 36: Trap and drain lines Item Description 3 in. minimum 2 in. minimum Installation Manual: YORK Sun™ Select YV28 to YV50 ® Johnson Controls Ducted Systems...
Table 5: Supply fan VFD weights Supply 208/230 V 460 V 575 V fan motor 7.5 HP 17.4 14.6 10 HP 17.4 14.6 15 HP 20.9 17.4 26.5 20 HP 17.4 26.5 Installation Manual: YORK Sun™ Select YV28 to YV50 ® Johnson Controls Ducted Systems...
The following figures show the roof curbs for the units. All dimensions are in inches. Return air Supply air Figure 37: 1RC0450 roof curb dimensions The following units are compatible with 1RC0450 roof curbs. • YV28 • YV30 • YV35 Installation Manual: YORK Sun™ Select YV28 to YV50 ® Johnson Controls Ducted Systems...
Page 28
Figure 38: 1RC0451 roof curb dimensions The following units are compatible with 1RC0451 roof curbs. • YV40 • YV50 Installation Manual: YORK Sun™ Select YV28 to YV50 ® Johnson Controls Ducted Systems...
1RB0401. This kit will aid in properly aligning the new unit with the existing roof curb. Units are shipped with compressor mountings that are factory-adjusted and ready for operation. Installation Manual: YORK Sun™ Select YV28 to YV50 ® Johnson Controls Ducted Systems...
The bracket and screw locations are shown in Figure 42. Figure 42: Metal bracket removal Item Description Metal bracket location Screws Metal bracket Installation Manual: YORK Sun™ Select YV28 to YV50 ® Johnson Controls Ducted Systems...
If any of the wire supplied with the unit must be replaced, replacement wire must be of the Item Description type shown on the wiring diagram and the same Filters minimum gauge as the replaced wire. Installation Manual: YORK Sun™ Select YV28 to YV50 ® Johnson Controls Ducted Systems...
Power wiring is brought into the unit through the side of the unit or the basepan inside the curb. Item Description Side entry patch plate Control box door Installation Manual: YORK Sun™ Select YV28 to YV50 ® Johnson Controls Ducted Systems...
56 in. above the floor. The respectively. Change the tap on the transformer for thermostat must not be subject to drafts, sun 208-3-60 operation. See the unit wiring diagram. Installation Manual: YORK Sun™ Select YV28 to YV50 ® Johnson Controls Ducted Systems...
Page 34
Figure 48: Typical electronic thermostat field wiring Installation Manual: YORK Sun™ Select YV28 to YV50 ® Johnson Controls Ducted Systems...
Remove the bolt and washer from all three latches of each hinged access panel. See Figure 50. Retain the removed latches for reinstallation in a later step. Installation Manual: YORK Sun™ Select YV28 to YV50 ® Johnson Controls Ducted Systems...
Figure 52: Toolless access handle assembly The convenience outlet cover is shipped in the floor of the control box as shown in Figure 54. Figure 54: Location of convenience outlet cover Installation Manual: YORK Sun™ Select YV28 to YV50 ® Johnson Controls Ducted Systems...
Page 37
208/230-3-60 units with a factory-installed powered convenience outlet option are wired for 230 V power supply. Change the tap on the transformer for 208-3-60 operation. Refer to the unit wiring diagram. Installation Manual: YORK Sun™ Select YV28 to YV50 ® Johnson Controls Ducted Systems...
Fan diameter (in.) Type Prop Prop Drive type Direct Direct Number of motors Motor HP each 1140 1140 Nominal total CFM 28530 29800 Belt drive evap fan data Installation Manual: YORK Sun™ Select YV28 to YV50 ® Johnson Controls Ducted Systems...
Page 63
15-25 35-50 Gas limit setting (ºF) (top/bottom) 140/160 140/140 Gas piping connection (in.) 1 1/4 1 1/4 Dimensions (in.) Length Width Height Operating weight (lb) 4191 5742 Installation Manual: YORK Sun™ Select YV28 to YV50 ® Johnson Controls Ducted Systems...
Page 64
3 - (20 x 25 x 4) 8 - (20 x 25 x 4) 3089 / 3603 3046 / 3690 5778 / 6566 5470 / 6217 ID Blower power (kW) Installation Manual: YORK Sun™ Select YV28 to YV50 ® Johnson Controls Ducted Systems...
Page 65
Fan diameter (in,) Type Prop Drive type Direct Number of motors Motor HP each 1200 Nominal total CFM 41676 Belt drive evap fan data Quantity Fan size (in.) 20x18 Installation Manual: YORK Sun™ Select YV28 to YV50 ® Johnson Controls Ducted Systems...
Proper sizing of gas piping depends on the cubic feet per hour of gas flow required, specific gravity of the gas, and the length of run. Installation Manual: YORK Sun™ Select YV28 to YV50 ® Johnson Controls Ducted Systems...
Page 67
90° elbow Reducer Union 7-in. long nipple 7-in. long nipple 90° elbow 28-in. pipe Caulk between pipe and base rail grommet to 3.7-in. long nipple provide watertight seal Installation Manual: YORK Sun™ Select YV28 to YV50 ® Johnson Controls Ducted Systems...
Note: Maximum capacity of pipe in cubic feet of gas per hour based upon a pressure drop of 0.3 in. W.C. and 0.6 specific gravity gas. Installation Manual: YORK Sun™ Select YV28 to YV50 ® Johnson Controls Ducted Systems...
All propane gas equipment must conform to the safety standards of the National Fire Protection Association. Installation Manual: YORK Sun™ Select YV28 to YV50 ® Johnson Controls Ducted Systems...
Page 70
Using the screws removed in Step 1, attach the upper flue exhaust hood as shown in Figure 62. For units with low gas heat, the installation is now complete. Installation Manual: YORK Sun™ Select YV28 to YV50 ® Johnson Controls Ducted Systems...
When the control determines that the outside air de-energized as long as their minimum run timers is suitable, the first stage of cooling is always free have expired. cooling. Installation Manual: YORK Sun™ Select YV28 to YV50 ® Johnson Controls Ducted Systems...
• De-energizes the exhaust fan when the economizer output is below the economizer damper position for exhaust fan off Installation Manual: YORK Sun™ Select YV28 to YV50 ® Johnson Controls Ducted Systems...
The MAT parameter reports input status (°F/°C), 3.65 VDC reading MAT (+) to Type III negative temperature coefficient thermistor COM (−) with open circuit. Read-only use in current control revision. Installation Manual: YORK Sun™ Select YV28 to YV50 ® Johnson Controls Ducted Systems...
Page 75
Lit/flickering indicates UCB-to-economizer board SA bus communication SA BUS SA BUS Green UCB SA bus communication transmission indicator is currently active, off indicates the economizer board is awaiting SA bus communication Installation Manual: YORK Sun™ Select YV28 to YV50 ® Johnson Controls Ducted Systems...
Page 76
24 VAC hot connection to power the economizer board. Connects through circuit 24 VAC transformer HOT traces to R/24V~ terminals and pins distributed on the economizer board. Installation Manual: YORK Sun™ Select YV28 to YV50 ® Johnson Controls Ducted Systems...
The scroll is misphased if it is drawing low amperage, has similar suction and discharge pressures, or it produces a high noise level. Installation Manual: YORK Sun™ Select YV28 to YV50 ® Johnson Controls Ducted Systems...
Page 78
To decrease belt tension, clear the top move all nuts (B or C) against bracket nuts (B) away from bracket and turn the lower nuts (C) against the bracket. Installation Manual: YORK Sun™ Select YV28 to YV50 ® Johnson Controls Ducted Systems...
Note: Blower performance includes gas heat exchangers and 2-in. filters. See the Static resistance table for additional applications. See the RPM selection table to determine the required motor sheave setting and to determine the maximum continuous BHP. kW = BHP x 0.93 Installation Manual: YORK Sun™ Select YV28 to YV50 ®...
Start the supply air blower motor. Adjust the resistances in both the supply and the return air duct systems to balance the air distribution throughout the conditioned space. The job Installation Manual: YORK Sun™ Select YV28 to YV50 ® Johnson Controls Ducted Systems...
Figure 69: Indoor Coil (dry coil + std. 2-in. filters) pressure drop versus supply air CFM Item Description Large cabinet (50 t) Small cabinet (35 t) Large cabinet (40 t) Small cabinet (27.5 t and 30 t) Installation Manual: YORK Sun™ Select YV28 to YV50 ® Johnson Controls Ducted Systems...
0.25 IWG, the unit delivers less CFM limitations shown in the blower performance during full economizer operation. tables. • You can adjust pulleys in half turn increments. • Adjust the belt tension. Installation Manual: YORK Sun™ Select YV28 to YV50 ® Johnson Controls Ducted Systems...
The FAN output for indoor fan operation and remains On until 24 V is present energizes with any cooling output after the again on the MV terminal. Fan On Delay for Cool expires. Installation Manual: YORK Sun™ Select YV28 to YV50 ® Johnson Controls Ducted Systems...
Low heat The ICB keeps the main gas valve and induced draft motor energized while continuously monitoring the call for heat, low pressure switch, and flame status. Installation Manual: YORK Sun™ Select YV28 to YV50 ® Johnson Controls Ducted Systems...
Measure the temperature drop across the evaporator coil. Measure the system amperage draw across all legs of 3 phase power wires. Measure the condenser fan amperage draw. Installation Manual: YORK Sun™ Select YV28 to YV50 ® Johnson Controls Ducted Systems...
Set the thermostat to the lowest temperature setting. Turn off all electrical power to unit. Open the gas heat access panel. Turn the gas valve switch to the OFF position. Installation Manual: YORK Sun™ Select YV28 to YV50 ® Johnson Controls Ducted Systems...
Page 89
For modulating furnaces, when commissioning is complete return the System Selection bottom pin jumper to NORM OPERATION on the Modulating Furnace Control. Installation Manual: YORK Sun™ Select YV28 to YV50 ® Johnson Controls Ducted Systems...
Btu content of the gas in your particular locality (contact your gas company for this information as it varies widely from area to area). Installation Manual: YORK Sun™ Select YV28 to YV50 ® Johnson Controls Ducted Systems...
COMMISSION mode to maintain full input. checked, adjust the thermostat to call for first After the temperature rise has been determined, the stage heat. CFM can be calculated as follows: Installation Manual: YORK Sun™ Select YV28 to YV50 ® Johnson Controls Ducted Systems...
Burner Disconnect wiring to the gas valve. Remove Orifice the manifold and gas valve assembly. Orifices Manifold can now be inspected and/or replaced. Installation Manual: YORK Sun™ Select YV28 to YV50 ® Johnson Controls Ducted Systems...
SD-24 and R 24 VAC common for thermostat power Installation Manual: YORK Sun™ Select YV28 to YV50 ® Johnson Controls Ducted Systems...
Page 97
Input required for operation of 2-compressor units, not active for 1-compressor units; 3.625 EC2+ input from 10KΩ @ 77°F, Type III negative temperature VDC reading EC2+ to EC2– with open circuit. Used in suction line temperature safety. coefficient thermistor Installation Manual: YORK Sun™ Select YV28 to YV50 ® Johnson Controls Ducted Systems...
Page 98
Not effective for one stage compressor UCBs. If demand is present and permissions 24 VAC hot output for compressor 2 allow compressor 2 operation; output with compressor cooling, comfort ventilation cooling or heat pump heating demands Installation Manual: YORK Sun™ Select YV28 to YV50 ® Johnson Controls Ducted Systems...
Page 99
ENTER Button for display menu acknowledgment and navigation Button for display menu navigation and zeroing of active compressor CANCEL ASCD timer 4-way Joystick for display menu navigation Installation Manual: YORK Sun™ Select YV28 to YV50 ® Johnson Controls Ducted Systems...
Page 100
UCB is awaiting incoming FC bus communication ISO PWR Green communication board Isolated Power indicator Lit indicates the UCB is supplying power to the communication sub-board Installation Manual: YORK Sun™ Select YV28 to YV50 ® Johnson Controls Ducted Systems...
Input required for heat pump units, not required for A/C units; 3.625 VDC reading CC4+ to CC4– CC4+ sensor input from 10KΩ @ 77°F, Type III negative with open circuit. Used in heat pump demand defrost calculation. temperature coefficient thermistor Installation Manual: YORK Sun™ Select YV28 to YV50 ® Johnson Controls Ducted Systems...
Page 102
HPS4 trips in a two hour period cause a “High Pressure Switch 4 Lockout” and C4 output is then Pressure Switch (left pin) prevented until alarm reset. Connects through circuit trace to the right LPS4 pin. Installation Manual: YORK Sun™ Select YV28 to YV50 ® Johnson Controls Ducted Systems...
We recommend 26 AWG solid, 6-wire (3 twisted pairs) cable as the best fit for fabricating modular cables with the modular jack housing assembly. Be sure the cable you use fits the modular jack housing. The preassembled cables that are available from Anixter (Part No. CBL-NETWORKxxx) use 24 gauge wire. Installation Manual: YORK Sun™ Select YV28 to YV50 ®...