York AFFINITY 292443-XTG-B-0807 Technical Manual
York AFFINITY 292443-XTG-B-0807 Technical Manual

York AFFINITY 292443-XTG-B-0807 Technical Manual

Affinity series (export only) single package gas/electric air cooled air conditioners 1.5 through 5 nominal ton

Advertisement

TECHNICAL GUIDE
AFFINITY™ SERIES
(EXPORT ONLY)
SINGLE PACKAGE GAS/ELECTRIC
AIR COOLED AIR CONDITIONERS
1.5 THROUGH 5 NOMINAL TON
DNA018 THROUGH 060
8.6 - 9.2 EER
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
SO 9001
Certified Quality
Management System
FLEXIBLE LIGHT COMMERCIAL UNIT
GENERAL
®
York
Affinity™ Series packaged units are designed to han-
dle applications ranging from residential to light commercial
and any in between. The Affinity™ is a unit that gives you the
flexibility and choices you need in today's market.
FEATURING
COOLING/GAS HEATING UNITS (NATURAL GAS OR
PROPANE)
LOW PROFILE
QUIET OPERATION
COMMON FOOTPRINT
OPTIONAL SLIDE IN MOTORIZED DAMPERS
OPTIONAL SLIDE IN ECONOMIZERS
OPTIONAL PROPANE CONVERSION KIT
OPTIONAL HIGH ALTITUDE CONVERSION KIT
(NATURAL GAS/PROPANE)
FULL PERIMETER BASE RAILS
BOTTOM AND SIDE UTILITY CONNECTIONS
292443-XTG-B-0807

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the AFFINITY 292443-XTG-B-0807 and is the answer not in the manual?

Questions and answers

Summary of Contents for York AFFINITY 292443-XTG-B-0807

  • Page 1 FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE FLEXIBLE LIGHT COMMERCIAL UNIT GENERAL ® York Affinity™ Series packaged units are designed to han- dle applications ranging from residential to light commercial and any in between. The Affinity™ is a unit that gives you the flexibility and choices you need in today’s market.
  • Page 2: Table Of Contents

    DESCRIPTION ......3 STANDARD FEATURES/BENEFITS ... . 3 FIELD-INSTALLED ACCESSORIES.
  • Page 3: Description

    292443-XTG-B-0807 DESCRIPTION These packaged cooling/heating air conditioners are designed for outdoor installation. Only utility and duct con- nections are required at the point of installation. The gas-fired heaters have aluminized steel tubular heat exchangers and spark to pilot ignition. They are available in natural gas with field conversion to propane.
  • Page 4: Field-Installed Accessories

    FAN SYSTEM - All models operate over a wide range of design conditions with a 3-speed direct-drive fan motor. These units easily match all types of applications and pro- vides greater on site flexibility to match comfort requirement. SIMPLE CONTROL CIRCUIT - A low voltage printed circuit board contains a diagnostic indicator light and a low voltage terminal strip.
  • Page 5: Unit Component Location

    292443-XTG-B-0807 required if Thermostat 2ET07700224 and 2ET04700224 are used. MOTORIZED FRESH AIR DAMPER - Designed for duct mounted side supply/return and unit mounted down supply/ return applications. Damper capable of providing 0% through 50% of outdoor air (field supplied). Closes on power loss, includes hood and screen assembly.
  • Page 6: Physical Data

    TABLE 1: PHYSICAL DATA MODEL CENTRIFUGAL BLOWER (Dia. x W. in.) EVAPORATOR BLOWER FAN MOTOR HP (3 Speed) ROWS DEEP EVAPORATOR FINS PER INCH COIL FACE AREA (Sq. Ft.) PROPELLER DIA. (in.) CONDENSER FAN MOTOR HP NOM. CFM TOTAL ROWS DEEP CONDENSER FINS PER INCH COIL...
  • Page 7: Dna018 Cooling Capacities - 1-1/2 Ton

    292443-XTG-B-0807 TABLE 3: DNA018 COOLING CAPACITIES - 1-1/2 TON TEMPERATURE 450 CFM OF AIR ON WB °F CONDENSER COIL NET CAP. 17.4 16.6 15.3 TOTAL POWER 1.78 1.77 1.72 INPUT kW 11.9 14.1 11.4 13.7 85 °F 11.0 13.2 10.5 12.7 10.0 12.3...
  • Page 8: Dna024 Cooling Capacities - 2 Ton

    TABLE 4: DNA024 COOLING CAPACITIES - 2 TON TEMPERATURE 600 CFM OF AIR ON WB °F CONDENSER COIL NET CAP. 24.1 22.5 20.9 TOTAL POWER 2.28 2.25 2.21 INPUT kW 12.9 16.5 19.7 12.3 15.9 19.1 85 °F 11.7 15.3 18.5 11.1 14.6...
  • Page 9: Dna030 Cooling Capacities - 2-1/2 Ton

    292443-XTG-B-0807 TABLE 5: DNA030 COOLING CAPACITIES - 2-1/2 TON TEMPERATURE 750 CFM OF AIR ON WB °F CONDENSER COIL NET CAP. 28.1 26.4 24.2 TOTAL POWER 2.99 2.95 2.90 INPUT kW 15.3 19.8 23.6 14.5 19.0 22.8 85 °F 13.7 18.2 22.1 13.0...
  • Page 10: Dna036 Cooling Capacities - 3 Ton

    TABLE 6: DNA036 COOLING CAPACITIES - 3 TON TEMPERATURE 900 CFM OF AIR ON WB °F CONDENSER COIL NET CAP. 36.7 34.6 31.9 TOTAL POWER 3.57 3.51 3.44 INPUT kW 19.8 25.2 29.9 18.9 24.3 29.0 85 °F 18.0 23.4 28.1 17.1 22.4...
  • Page 11: Dna042 Cooling Capacities - 3-1/2 Ton

    292443-XTG-B-0807 TABLE 7: DNA042 COOLING CAPACITIES - 3-1/2 TON TEMPERATURE 1,050 CFM OF AIR ON WB °F CONDENSER COIL NET CAP. 44.5 40.8 37.6 TOTAL POWER 4.01 4.00 3.85 INPUT kW 23.6 29.7 35.1 22.5 28.6 34.0 85 °F 21.4 27.5 32.9 20.3...
  • Page 12: Dna048 Cooling Capacities - 4 Ton

    TABLE 8: DNA048 COOLING CAPACITIES - 4 TON TEMPERATURE 1,200 CFM OF AIR ON WB °F CONDENSER COIL NET CAP. 48.5 45.0 41.0 TOTAL POWER 3.99 3.93 3.87 INPUT kW 28.9 36.8 41.0 25.5 33.4 40.3 85 °F 22.0 30.0 36.9 18.6 26.5...
  • Page 13: Dna060 Cooling Capacities - 5 Ton

    292443-XTG-B-0807 TABLE 9: DNA060 COOLING CAPACITIES - 5 TON TEMPERATURE 1,500 CFM OF AIR ON WB °F CONDENSER COIL NET CAP. 60.3 56.2 52.0 TOTAL POWER 5.67 5.58 5.48 INPUT kW 39.5 47.7 52.0 35.2 43.4 50.6 85 °F 31.0 39.1 46.4 26.7...
  • Page 14: Bottom Supply Air Blower Performance

    TABLE 10: SIDE SUPPLY AIR BLOWER PERFORMANCE MODEL # 1432 650 1381 628 1330 605 1279 583 1210 556 1140 529 1071 502 1191 527 1149 510 1107 494 1065 477 1009 459 1681 797 1610 768 1540 740 1465 712 1390 685 1315 657 1204 623 1093 588 1432 650 1381 628 1330 605 1279 583 1210 556 1140 529 1191 527 1149 510 1107 494 1065 477 048,060...
  • Page 15: Typical Field Control Wiring Diagram

    292443-XTG-B-0807 TABLE 12: ADDITIONAL STATIC PRESSURE RESISTANCE 1-1/2 - 3-1/2 TON (DNA018 - 042) DESCRIPTION WET EVAPORATOR COIL ECONOMIZER FILTER FRAME KIT 1. Deduct these resistance values from the available external static pressure shown in Tables 10 and 11. 2. The pressure through the economizer is greater for 100% outdoor air then for 100% return air. If the resistance of the return air duct system is less then 0.25 IWG, the unit will deliver less CFM during full economizer operation.
  • Page 16: Typical Field Power Wiring Diagram

    FIGURE 4 - TYPICAL FIELD POWER WIRING DIAGRAM TABLE 14: ELECTRICAL DATA VOLTAGE LIMITATIONS MODEL POWER SUPPLY MIN. MAX. 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60 1. Utilization range “A” in accordance with ARI Standard 110. 2. Dual element, time delay type. REFER TO ELECTRICAL DATA TABLES TO SIZE THE DISCONNECT...
  • Page 17: Unit Dimensions - Front

    292443-XTG-B-0807 B L O W E R S E R V I C E A C C E S S C O M P A R T M E N T P A N E L G A S S U P P L Y 1 - 1 / 4 "...
  • Page 18: Unit Dimensions - Front & Bottom

    FIGURE 6 - UNIT DIMENSIONS - FRONT & BOTTOM FIGURE 7 - UNIT DIMENSIONS - BACK & BOTTOM 292443-XTG-B-0807 Unitary Products Group...
  • Page 19: Typical Slab On Ground Installation

    292443-XTG-B-0807 FIGURE 8 - TYPICAL SLAB ON GROUND INSTALLATION FIGURE 9 - TYPICAL ROOF CURB INSTALLATION Unitary Products Group...
  • Page 20: Typical Duct Applications

    FIGURE 10 - TYPICAL DUCT APPLICATIONS TABLE 17: UNIT WEIGHTS AND CENTER OF GRAVITY SHIPPING OPERATING UNIT WEIGHT WEIGHT SIZE (lbs.) FIGURE 11 - UNIT CENTER OF GRAVITY CORNER WEIGHTS (location, lbs.) (lbs.) “A” “B” “C” "D" FRONT UNIT "A" 49-1/8 "B"...
  • Page 21: Roof Curb Dimensions

    292443-XTG-B-0807 FIGURE 12 - ROOF CURB DIMENSIONS 1. 8” Roof curb also available FIGURE 13 - ROOF CURB CROSS SECTION Unitary Products Group...
  • Page 22: Typical Wiring Diagram Dna 018 Thru 060 (208/230-1-60 Power Supply)

    FIGURE 14 - TYPICAL WIRING DIAGRAM DNA 018 THRU 060 (208/230-1-60 POWER SUPPLY) 292443-XTG-B-0807 Unitary Products Group...
  • Page 23: Typical Wiring Diagram Notes

    MECHANICAL SPECIFICATIONS GENERAL Units shall be manufactured by York International Unitary Products Group in an ISO 9001 certified facility. YORK’s Affinity™ package units are designed to handle applications ranging from residential to light commercial and any in between. The Affinity™ is a unit that gives you the flexibility and choices you need in today’s market.
  • Page 24 All unit power wiring shall enter unit cabinet at a single factory provided location and be capable of side or bottom entry, to minimize roof penetrations and avoid unit field modifications. Separate side and bottom openings shall be provided for the control wiring. Supersedes: 292443-XTG-A-0207 5005 York Drive 292443-XTG-B-0807 Norman 73069...

Table of Contents