SPECIFICATIONS
This chapter describes the performance specifications.
2.1

Performance Specifications

This section describes the performance specifications of the D/A converter modules.
R60DA4
Item
Number of analog output points
Digital input
Analog output voltage
Analog output current
I/O characteristics, resolution
Accuracy (accuracy for the maximum
value of the analog output value)
Conversion
Normal output
speed
mode
Wave output
mode
Number of offset/gain settings
Output short protection
Isolation method
Withstand voltage
Insulation resistance
Number of occupied I/O points
External connection system
Applicable wire size
Applicable solderless terminal
External power supply
Internal current consumption (5VDC)
External
Height
dimensions
Width
Depth
Weight
*1 For details on the I/O conversion characteristic, refer to the following.
Page 54 I/O Conversion Characteristics
*2 Except for the conditions under noise influence.
*3 A count more than 50000 times causes Number of writes to offset/gain settings reach limit error (error code: 1080H).
*4 The maximum resolution of the user range setting
2 SPECIFICATIONS
16
2.1 Performance Specifications
Specifications
4 points (4 channels)
16-bit signed binary value (-32768 to 32767)
-10 to 10VDC (external load resistance value 1k or more)
0 to 5VDC (external load resistance value 500 or more)
0 to 20mADC (external load resistance value 0 to 600)
*1
Analog output range
Voltage
0 to 5V
1 to 5V
-10 to 10V
User range setting (voltage)
Current
0 to 20mA
4 to 20mA
User range setting (current)
Ambient temperature 25 5: Within 0.1% (Voltage 10mV, current 20A)
*2
Ambient temperature 0 to 55: Within 0.3% (Voltage 30mV, current 60A)
80s/CH
80s/CH
*3
Up to 50000 times
Protected
Between I/O terminals and programmable controller power supply: Photocoupler
Between output channels: Non-isolation
Between the external power supply and analog outputs: Transformer isolation
Between I/O terminals and programmable controller power supply: 500VACrms for 1 minute
Between the external power supply and analog outputs: 500VACrms for 1 minute
Between I/O terminals and programmable controller power supply: 10M or higher, at 500VDC
16 points (I/O assignment: Intelligent 16 points)
18-point terminal block
0.3 to 0.75
R1.25-3 (solderless terminal with an insulation sleeve cannot be used)
24VDC +20%, -15%
Ripple, spike 500mV
P-P
Inrush current: 5.0A, 690s or shorter
Current consumption: 0.14A (at 24VDC)
0.16A
106mm (Base unit mounting side: 98mm)
27.8mm
131mm
0.19kg
Digital value
0 to 32000
-32000 to 32000
0 to 32000
-32000 to 32000
or lower
Resolution
156.3V
125.0V
312.5V
*4
312.5V
625.0nA
500.0nA
350.9nA