CONFIGURATION SCREENS
Parameter
Silnt Mde Cntrl Loc
ODU Cyc Prio
Therm Off Delay
32
4/4 Installer / General
Silnt Mde Cntrl Loc
ODU Cyc Prio (56)
Therm Off Delay (56)
Parameter Settings
Choices: 0 = "ODU(0)"
1 = "Remote1(1)"
Default value = ODU(0)
Choices: "Disable" "Standby(1) "Prio
Cool(2)"
Default value = "Disable"
Choices: "45 min(0)"
"30 min(1)"
"60 min(2)" "90 min(3)" "120 min(4)"
Default value = "45 min(0)"
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
ODU (0)
Prio Cool (2)
45 Min (0)
Definition
Reduces the refrigerant noise during IDU initialization in
heating mode
When ODU Cyc Prio(56) is set to Standby(1) on the
CRC1, if the ODU is in cooling mode and the slave IDU
calls for heating, the slave IDU goes thermal off and
stays in cooling mode.
When ODU Cyc Prio(56) is set to Priority Cool(2) on the
CRC1, if the ODU is in heating mode and the slave IDU
calls for cooling, the IDU will wait the amount of time set
by Therm Off Delay(56) after the master IDU is heating
thermal satisfied and the ODU will then switch to cooling
mode.
Time duration for IDU thermal off delay.