CONFIGURATION SCREENS
Outdoor Unit Control
Press the Outdoor Unit Control button on the Building Manager screen to display the Outdoor Unit Control screen. The Out-
door Unit Control lets you manage outdoor units through the controller interface.
NOTE:
For the first four controls to be visible, ODU Mode - M/S(47) control must be set to "Master(1)." For the Silent Mode Start/End con-
trols to be usable, Silnt Mde Cntrl Loc control on Configuration/Installer General 4/4 screen must be set to "Remote(1)."
Parameter
Defrost/Snow(49)
Smart load contrl
Eco. Cool(44)
Ref. Noise Red.(48)
Silent Mode Start/End
28
O u t d oo r U n i t C o nt r ol
D efro st/ Sn ow(49)
Sm art l o ad contr l
E co. C oo l (44)
Ref. Noise Red. (48)
S il en t Mo d e Star t
Si len t Mo de End
Parameter Settings
0 = "Disable (0)"
1 = "Snow Rmvl (1)"
2 = "Fast Dfrst (2)"
3 = "Both (3)"
Default value = Disable(0)
0 = "Disable (0)"
1 = "Efficient (1)"
2 = "Normal (2)"
3 = "Power (3)"
Default value = Disable(0)
0 = "Disable (0)"
1 = "Low-Savings (1)"
2 = "Mid-Savings (2)"
3 = "Hi-Savings (3)"
Default value = Disable(0)
Choices: Disable(0), Mode 1 (1), Mode 2 (2)
Default value = Disable(0)
Default value = "--:--"
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
S now Rmv l( 1 )
N or mal ( 2)
D i sable (0 )
D i sable (0 )
--: - -
--: - -
Enables the defrost function to remove
snow from the outdoor unit
Changes target/head suction pressure to
maximize energy savings and minimize time
to set point
Reduces the refrigerant noise during the
initialization of the indoor unit in heating
mode.
Time of day in either AM/PM or 24 hr. format
(depending on control setting in Display /
Date & Time section)
Set start time and end time
for Silent Mode
Definition