10.3.

Functional check

WARNING
Danger of fatal injury as a result of faults in installation and functional check.
Ì
Before carrying out the functional check, make sure that there are no persons in the danger zone.
Ì
Observe the valid accident prevention regulations.

10.3.1. Electrical function test

After installation and any fault, the safety function must be fully checked. Proceed as follows:
1. Switch on operating voltage.
The machine must not start automatically.
¨
The safety switch carries out a self-test. The green STATE LED then flashes at regular intervals.
¨
2. Close all guards.
The machine must not start automatically.
¨
The green STATE LED illuminates continuously.
¨
3. Enable operation in the control system.
4. Open the guard.
The machine must switch off and it must not be possible to start it as long as the guard is open.
¨
The green STATE LED flashes at regular intervals.
¨
Repeat steps 2 - 4 for each guard.
2112663-08-02/20 (Translation of the original operating instructions)
Non-Contact Safety Switch CES-AP-C01-...
Operating Instructions
17
EN