Advertisement

Jetter AG

4.4 Environmental conditions

4.5 EMI values

4.5.1 Housing

Emitted interfer-
ence
Immunity to inter-
ference
JX3-BN-EC User Manual
Category
Operating temperature
Storage temperature
Air humidity
Max. operating altitude:
Corrosion immunity and
chemical resistance
Degree of pollution - Elec-
tronics
Tab. 5: Environmental conditions
Parameter
Frequency band
Limit value
Frequency band
Limit value
Tab. 6: Emitted interference
Parameter
Magnetic field with mains frequency
Frequency
Magnetic field
RF field, amplitude-modulated
Frequency band
Test field strength
ESD
Discharge through air:
Test peak voltage 8 kV
Discharge through air
Test peak voltage
Tab. 7: Immunity to interference
Description
0 ... +50 °C
-40 ... +70 °C
10 ... 95 %,
non-condensing
2,000 m above sea level
No special protection against corrosion. Ambient air
must be free from higher concentrations of acids, al-
caline solutions, corrosive agents, salts, metal va-
pors, and other corrosive or electroconductive con-
taminants.
Degree of pollution 2
Usually, the pollution is non-conductive. However,
temporary conductivity due to condensation may oc-
cur.
Values
30 ... 230 MHz
30 dB (µV/m) at 10 m dis-
tance
230 ... 1,000 MHz
37 dB (µV/m) at 10 m dis-
tance
Class B
Values
50 Hz
30 A/m
80 MHz ... 2 GHz
10 V/m
AM 80 % with 1 kHz
Criterion A
8 kV
4 kV
Criterion A
Technical specifications | 4
Standards
DIN EN 61131-2
DIN EN 60068-2-1
DIN EN 60068-2-2
DIN EN 61131-2
Standards
DIN EN 61000-6-3
DIN EN 61131-2
DIN EN 55011
Standards
DIN EN 61131-2
DIN EN 61000-6-2
DIN EN 61000-4-8
DIN EN 61131-2
DIN EN 61000-6-2
DIN EN 61000-4-3
DIN EN 61131-2
DIN EN 61000-6-2
DIN EN 61000-4-2
13 / 92