Input Variables; Output Variables - GE AF-600 FP Operating Instructions Manual

Lonworks
Hide thumbs Also See for AF-600 FP:
Table of Contents

Advertisement

5.3 VSD 6010 Profile
5.3.1 Introduction
The Variable Speed Drive 6010 profile is a LonMark standardized functional profile.
It describes how to control a variable speed frequency converter.
For example, an air handling unit controller that sends messages to facilitate control of the start/stop and speed reference of the VSD. The VSD will deliver messages
such as the actual frequency converter speed and output current to the controller, operating interfaces and energy management systems.

5.3.2 Input Variables

Variable function
Drive speed setpoint

5.3.3 Output Variables

Variable function
Variable name
Drive speed
nvoDrvSpeed
Output current
nvoDrvCurnt
Output voltage
nvoDrvVolt
Output power
nvoDrvPwr
Running hours
nvoDrvRunHours
Variable name
nviDrvSpeedStpt
SNVT type
SNVT_lev_percent
SNVT_amp
SNVT_volt
SNVT_power_kilo
SNVT_time_hour
SNVT type
Profile
SNVT_switch
VSD 6010
Profile
VSD 6010
VSD 6010
VSD 6010
VSD 6010
VSD 6010
AF-600 FP LonWorks
5
AF-600 FP parameter
CTW / Reference
AF-600 FP parameter
DR-05
DR-14
DR-12
DR-10
ID-01
29