GE AF-600 FP Operating Instructions Manual page 43

Lonworks
Hide thumbs Also See for AF-600 FP:
Table of Contents

Advertisement

AF-600 FP LonWorks
Bit 09, Local operation / bus control:
Bit 09 set to [0] means that [STOP/RESET] is activated on the control unit or that Local [2] control in par. F-02 Operation Method is selected. It is not possible to
control the frequency converter via serial communication.
Bit 09 set to [1] means that it is possible to control the frequency converter via the network / serial communication interface.
Bit 10, Out of frequency limit:
Bit 10 set to [0] enables the output frequency to reach the value in par. F-18 Motor Speed Low Limit [RPM] or par. F-17 Motor Speed High Limit [RPM].
Bit 10 set to [1] means that the output frequency is within the defined limits.
Bit 11, No operation / in operation:
Bit 11 set to [0] means that the motor is not running.
Bit 11 set to [1] means that the frequency converter has received a start signal or that the output frequency is greater than 0 Hz.
Bit 12, Brake OK / Brake warning or failure:
Bit 12 = [0] means that there is no brake warning or failure present.
Bit 12 = [1] means that the drive has stopped because of a brake warning or failure.
Bit 13, Voltage OK / limit exceeded:
Bit 13 set to [0] means that there are no voltage warnings.
Bit 13 set to [1] means that the DC voltage in the frequency converter's intermediate circuit is too low or too high.
6
Bit 14, Torque OK / limit exceeded:
Bit 14 set to [0] means that the motor current is lower than the torque limit selected in par. F-43 Current Limit.
Bit 14 set to [1] means that the torque limit in par. F-43 Current Limit has been exceeded.
Bit 15, Timer OK / limit exceeded:
Bit 15 = [0] means that the timers for motor thermal protection and drive thermal protection, respectively, have not exceeded 100%.
Bit 15 = [1] means that one of the timers has exceeded 100%.
42

Advertisement

Table of Contents
loading

Table of Contents