GE AF-600 FP Operating Instructions Manual page 22

Lonworks
Hide thumbs Also See for AF-600 FP:
Table of Contents

Advertisement

Analog Output (X30 / 8)
Variable
SNVT
name:
type:
nvi101AnOut1
SNVT_lev_percent
NB!
This output variable applies only if the General Purpose I/O option (OPCSGPIO) is installed in the frequency converter.
This variable controls the X30/8 analog output on the OPCGPIO field installed option module as 0-20 mA or 4-20 mA.
In order to control output X30/8 via LonWorks, par. AN-60 Terminal X30/8 Output must be set to one of the following options:
[139] Bus ctrl. 0-20 mA
[140] Bus crtl. 4-20 mA
[141] Bus crtl. 0-20 mA Timeout
[142] Bus crtl. 4-20 mA Timeout
Function:
Bus crtl. 0-20 mA [139]: The output is controlled via bus. In the event of bus timeout, the output level remains unchanged.
Bus crtl. 4-20 mA [140]: The output is controlled via bus. In the event of bus timeout, the output level remains unchanged.
Bus crtl. 0-20 mA [141]: The output is controlled via bus. In the event of bus timeout, the output level is set to the predefined level in par. AN-64 Terminal X30/8
Output Timeout Preset.
Bus crtl. 4-20 mA [142]: The output is controlled via bus. In the event of bus timeout, the output level is set to the predefined level in par. AN-64 Terminal X30/8
Output Timeout Preset.
Analog Output (X42 / 7) (OPCGPIO only)
Variable
SNVT
name:
type:
nvi109AnOut1
SNVT_lev_percent
Analog Output (X42 / 9) (OPCGPIO only)
Variable
SNVT
name:
type:
nvi109AnOut2
SNVT_lev_percent
Analog Output (X42 /11) (OPCGPIO only)
Variable name:
SNVT type:
nvi109AnOut3
SNVT_lev_percent
Value:
Min.:
Max.:
0 %
100 %
Value:
Min.:
Max.:
0 %
100 %
Value:
Min.:
Max.:
0 %
100 %
Value:
Min.:
Max.:
0 %
100 %
AF-600 FP LonWorks
Resulution:
0.01 %
5
Resulution:
0.01 %
Resulution:
0.01 %
Resulution:
0.01 %
21