5.1.3 Drive VSD Profile
The drive VSD Profile describes all GE drive specific network variables.
5
Input variables
Variable Function
Start/Stop
Control word
Reset fault
Reference [%]
Reference [Hz]
CL Setpoint 1
CL Setpoint 2
CL Setpoint 3
Bus feedback 1
Bus feedback 2
Bus feedback 3
Digital/relay outputs
Analog output (42)
Analog output (X30/8)
Analog output (X42/7)
Analog output (X42/9)
Analog output (X42/11)
Setting of RTC
Parameter access command nviParamRequest
16
Variable Name
SNVT type
nviStartStop
SNVT_switch
nviControlword
SNVT_state
nviResetFaut
SNVT_switch
nviRefPcnt
SNVT_lev_percent
nviRefHz
SNVT_freq_hz
nviSetpoint1
SNVT_lev_percent
nviSetpoint2
SNVT_lev_percent
nviSetpoint3
SNVT_lev_percent
nviFeedback1
SNVT_lev_percent
nviFeedback2
SNVT_lev_percent
nviFeedback3
SNVT_lev_percent
nviDigiOutput
SNVT_state_64
nviAnOut1
SNVT_lev_percent
nvi101AnOut1
SNVT_lev_percent
nvi109AnOut1
SNVT_lev_percent
nvi109AnOut2
SNVT_lev_percent
nvi109AnOut3
SNVT_lev_percent
nviTimeStamp
SNVT_time_stamp
UNVT_param_request
AF-600 FP LonWorks
Profile
AF-600 FP Par.
Drive VSD
CTW/reference
Drive VSD
CTW
Drive VSD
CTW
Drive VSD
Reference
Drive VSD
Reference
Drive VSD
CL-21
Drive VSD
CL-22
Drive VSD
CL-23
Drive VSD
O-94
Drive VSD
O-95
Drive VSD
O-96
Drive VSD
E-90
Drive VSD
AN-53
Drive VSD
AN-63
Drive VSD
AO-43
Drive VSD
AO-53
Drive VSD
AO-63
Drive VSD
K-70
Drive VSD
-

Advertisement