GE AF-600 FP Operating Instructions Manual page 29

Lonworks
Hide thumbs Also See for AF-600 FP:
Table of Contents

Advertisement

Analog Input (X42/1)
Variable
name:
nvo109AnIn1
Analog Input (X42/3)
Variable
name:
5
nvo109AnIn2
Analog Input (X42/5)
Variable
name:
nvo109AnIn3
These variables contain the value allocated to the analog input terminal X42/1-5 of the (OPCAIO) Analog I/O Option Module. The variable type is changeable with
the commissioning tool.
NB!
This variable is available only if the Analog I/O Option Module (OPCAIO) has been installed in the frequency converter.
Parameter Access Response
Variable name:
nvoParamResponse
This output variable is used for the frequency converter access.
A special UNVT has been defined for this variable.
For more information on parameter access, please refer to the How to Access AF-600 FP Parameters section.
28
SNVT
type:
Changeable
SNVT_volt
SNVT_temp_p
SNVT_lev_percent
SNVT
type:
Changeable
SNVT_volt
SNVT_temp_p
SNVT_lev_percent
SNVT
type:
Changeable
SNVT_volt
SNVT_temp_p
SNVT_lev_percent
Value:
Min.
Max.
0 V
10 V
-273.15 °C
327.66 °C
0 %
100 %
Value:
Min.
Max.
0 V
10 V
-273.15 °C
327.66 °C
0 %
100 %
Value:
Min.
Max.
0 V
10 V
-273.15 °C
327.66 °C
0 %
100 %
SNVT type:
UNVT_param_response
AF-600 FP LonWorks
Resolution:
0.1 V
0.01 °C
0,1 %
Resolution:
0.1 V
0.01 °C
0,1 %
Resolution:
0.1 V
0.01 °C
0,1 %