Siemens SICAM Q100 System Manual page 82

Class a power quality instrument and power monitoring device
Hide thumbs Also See for SICAM Q100:
Table of Contents

Advertisement

Communication
2.2 Modbus
2.2.7.55 Registers 30001 to 30032: Measured Values for the Wind Farm Mode (Read
Only)
These registers are only available if you have activated the Wind Farm mode.
These registers are write-protected. A write attempt will be rejected with exception code 02
(ILLEGAL_DATA_ADDRESS).
Data type: Measured value
Table 2-65
Register
30001
30003
30005
30007
30009
30011
30013
30015
30017
30019
30021
30023
30025
30027
30029
82
Registers 30001 to 30032: Measured Values for the Wind Farm Mode
Type of Information
Firmware version
(string, 4 characters)
Frequency
Voltage Avg ph-ph
Active power
Reactive power
U positive sequence
U negative sequence
U zero sequence
I positive sequence
I negative sequence
I zero sequence
Uab RMS
Ubc RMS
Uca RMS
Start of sample period
(number of milliseconds since 1970-01-01 00:00 UTC)
Unit
-
Hz
V
W
var
V
V
V
A
A
A
V
V
V
-
SICAM Q100, 7KG95xx, System Manual
E50417-C1040-C522-A8, Edition 09.2020