Siemens SICAM Q100 System Manual page 64

Class a power quality instrument and power monitoring device
Hide thumbs Also See for SICAM Q100:
Table of Contents

Advertisement

Communication
2.2 Modbus
Table 2-40
Register
3201
3203 to
3298
2.2.7.32 Registers 3301 to 3756: Tariff Values (Read Only)
NOTE
Registers 3301 to 3756 are not available in SICAM PQS.
Data type: Measured value
The following table shows the general information (3301 to 3304) and values for the tariff 1 (3405 to 3448). The
values of the other 7 tariffs (3449 to 3756) are in the same structure.
Table 2-41
Register
3301
3302
3303
3304
3405
3409
3413
3417
3421
3425
3429
3433
3437
3441
64
Registers 3001 to 3298: PQ Calculation for Maximum Harmonics - Current Values
Type of Information
H_Ic-1_MAX
H_Ic-x_MAX
(x = 2 to 49)
Registers 3301 to 3448: Values of Tariff 1
Type of Information
Milliseconds
Hours/minutes
Month/day
Time status/year
WP_exp_tariff_value_1
WP_imp_tariff_value_1
WQ_ind_imp_tariff_value_1
WQ_cap_exp_tariff_value_1
WQ_ind_exp_tariff_value_1
WQ_cap_imp_tariff_value_1
WQ_ind_tariff_value_1
WQ_cap_tariff_value_1
WQ_imp_tariff_value_1
WQ_exp_tariff_value_1
Remark
Harmonic (average value), current value, c
(Fundamental)
Harmonic (average value), current value, c
(2 bytes for each register)
Remark
see chapter 2.2.6.2
Active Energy, Export, Tariff 1
Active Energy, Import, Tariff 1
Reactive Energy, Inductive, Import, Tariff 1
Reactive Energy, Capacitive, Export, Tariff 1
Reactive Energy, Inductive, Export, Tariff 1
Reactive Energy, Capacitive, Import, Tariff 1
Reactive Energy, Inductive, Tariff 1
Reactive Energy, Capacitive, Tariff 1
Reactive Energy, Import, Tariff 1
Reactive Energy, Export, Tariff 1
Unit
A
A
Unit
-
-
-
-
Wh
Wh
varh
varh
varh
varh
varh
varh
varh
varh
SICAM Q100, 7KG95xx, System Manual