2.2.7.54 Registers 23001 to 27608: Latest 288 Energy Profiles (Read Only)
You can read the data of the energy profiles during the latest 288 intervals via the Modbus TCP registers. These
registers are write-protected. A write attempt will be rejected with exception code 02
(ILLEGAL_DATA_ADDRESS).
Date type: Measured value +Date/time
The following table shows the data of the energy profile during the latest interval (23001 to 23016). The data
of the energy profiles during the other 287 intervals (23017 to 27608) are in the same structure.
Table 2-64
Register
23001
23002
23003
23004
23005 to 23006
23007 to 23008
23009 to 23010
23011 to 23012
23013 to 23014
23015
23016
SICAM Q100, 7KG95xx, System Manual
E50417-C1040-C522-A8, Edition 09.2020
Registers 23001 to 23016: The Latest 288 Energy Profiles (During the Latest Interval)
Type of Information
Milliseconds
Hours/minutes
Month/day
Year
WP_exp
WQ_exp
WP_imp
WQ_imp
WS
Quality
Reserved
Unit
Remark
End time of energy profile
For data format, see chapter 2.2.6.2.
kWh
Active energy export
kVARh
Reactive energy export
kWh
Active energy import
kVARh
Reactive energy import
kVAh
Apparent energy
-
bit 0 = 1: The energy profile is not calculated.
bit 0 = 0: The energy profile is calculated.
bit 1 = 1: Auxiliary power fails.
bit 1 = 0: Auxiliary power works well.
bit 2 = 1: Device starts up.
bit 2 = 0: Device works well.
bit 3 = 1: Time jumps.
bit 3 = 0: Time does not jump.
-