Siemens SICAM Q100 System Manual page 66

Class a power quality instrument and power monitoring device
Hide thumbs Also See for SICAM Q100:
Table of Contents

Advertisement

Communication
2.2 Modbus
Data type: Measured value
Table 2-43
Register
4379
4381 to
4504
4505
4507 to
4630
4631
4633 to
4756
2.2.7.35 Registers 5001 to 5099: Latest 10 Dips (Read Only)
These registers are write-protected. A write attempt will be rejected with exception code 02
(ILLEGAL_DATA_ADDRESS).
Data type: Measured value + Date/time
The following table shows the information for the latest dip (5001 to 5009). The information of the other 9 dips
(5011 to 5099) are in the same structure.
Table 2-44
Register
5001
5002
5003
5004
5005 to 5006
5007 to 5008
5009
66
Registers 4379 to 4756: Phase Angle of Harmonics - Current Values
Type of Information
HP_Ia-1
HP_Ia-x
(x = 2 to 63)
HP_Ib-1
HP_Ib-x
(x = 2 to 63)
HP_Ic-1
HP_Ic-x
(x = 2 to 63)
Registers 5001 to 5009: The Latest Dip
Type of Information
Milliseconds
Hours/minutes
Month/day
Time status/year
Voltage dip 1
Voltage dip 1 time duration
Influenced phase
Remark
Harmonic (phase angle), current value, a
(fundamental)
Harmonic (phase angle), current value, a
(2 bytes for each register)
Harmonic (phase angle), current value, b
(fundamental)
Harmonic (phase angle), current value, b
(2 bytes for each register)
Harmonic (phase angle), current value, c
(fundamental)
Harmonic (phase angle), current value, c
(2 bytes for each register)
Unit
Remark
Start time of dip
Data format see chapter 2.2.6.2
V
Minimum voltage value during dip 1
s
Dip 1 time duration
-
Related phases
bit 0: Va, bit 1: Vb, bit 2: Vc,
bit 3: Vab, bit 4: Vbc, bit 5: Vca
if any bit =1 means corresponding phase
is influenced
Unit
° (degree)
° (degree)
° (degree)
° (degree)
° (degree)
° (degree)
SICAM Q100, 7KG95xx, System Manual
E50417-C1040-C522-A8, Edition 09.2020