Siemens SICAM Q100 System Manual page 71

Class a power quality instrument and power monitoring device
Hide thumbs Also See for SICAM Q100:
Table of Contents

Advertisement

Table 2-50
Type of Flags
LOADPROFILE_FLAG_Q1
LOADPROFILE_FLAG_QTOT
LOADPROFILE_FLAG_QMIXED
2.2.7.41 Registers 6101 to 6158: Load Profile – Measured Values (Read Only)
These registers are write-protected. A write attempt will be rejected with exception code 02
(ILLEGAL_DATA_ADDRESS).
Data type: Measured value
Table 2-51
Register
6101
6103
6105
6107
6109
6111
6113
6115
6117
6119
6121
6123
6125
6127
6129
6131
SICAM Q100, 7KG95xx, System Manual
E50417-C1040-C522-A8, Edition 09.2020
Last period information - Flags (cont.)
Registers 6101 to 6158: Load Profile – Measured Values
Type of Information
Total power factor import (previous period)
Total power factor export (previous period)
Average active power import (previous period)
Average active power export (previous period)
Average reactive power import (previous period)
Average reactive power export (previous period)
Average apparent power (previous period)
Cumulated active power import (previous period)
Cumulated active power export (previous period)
Cumulated reactive power import (previous period)
Cumulated reactive power export (previous period)
Cumulated apparent power (previous period)
Maximum active power (previous period)
Minimum active power (previous period)
Maximum reactive power (previous period)
Minimum reactive power (previous period)
Flag
Remark
0x00000040
Reactive power = Q1
0x00000020
Reactive power = Qtot
0x00000010
Reactive power was changed
in subperiod
Communication
2.2 Modbus
Unit
-
-
W
W
var
var
VA
W
W
var
var
VA
W
W
var
var
71