2.2.7.43 Registers 6801 to 6804: CO
These registers are write-protected. A write attempt will be rejected with exception code 02
(ILLEGAL_DATA_ADDRESS).
Data type: Measured value
Table 2-53
Register
6801
6803
2.2.7.44 Registers 7001 to 7378: Prevailing Phase Angle of Harmonics – Voltage
Values (Read Only)
These registers are write-protected. A write attempt will be rejected with exception code 02
(ILLEGAL_DATA_ADDRESS).
Reference rate: Aggregation time
Network types: Only 1P2W, 3P4W_bal, 3P4W_unb_PN is available.
Data type: Measured value
Table 2-54
Register
7001
7003 to
7126
7127
7129 to
7252
7253
7255 to
7378
SICAM Q100, 7KG95xx, System Manual
E50417-C1040-C522-A8, Edition 09.2020
2
Registers 6801 to 6804: CO
Type of Information
CO
emissions of WP_imp
2
CO
emissions of WP_exp
2
Registers 7001 to 7378: Prevailing Phase Angle of Harmonics – Voltage Values
Type of Information
HPP_Va-1
HPP_Va-x
(x = 2 to 63)
HPP_Vb-1
HPP_Vb-x
(x = 2 to 63)
HPP_Vc-1
HPP_Vc-x
(x = 2 to 63)
Emissions (Read Only)
Emissions
2
Remark
Harmonic (prev. phase angle), voltage value, a-N
(fundamental)
Harmonic (prev. phase angle), voltage value, a-N
(2 bytes for each register)
Harmonic (prev. phase angle), voltage value, b-N
(fundamental)
Harmonic (prev. phase angle), voltage value, b-N
(2 bytes for each register)
Harmonic (prev. phase angle), voltage value, c-N
(fundamental)
Harmonic (prev. phase angle), voltage value, c-N
(2 bytes for each register)
Communication
2.2 Modbus
Unit
t
t
Unit
° (degree)
° (degree)
° (degree)
° (degree)
° (degree)
° (degree)
73