KROHNE OPTIMASS Series Handbook page 66

Mass flowmeters and 050/051 converters
Table of Contents

Advertisement

Fct.
Text
No
4.8
SYS.CTROL
4.8.1
FUNCTION
4.8.2
CONDITION
4.8.3
LOW LIMIT
4.8.4
HIGH LIMIT
4.9
COMM.MODULE
4.9.1
PROTOCOL
4.9.2
ADDRESS
4.9.3
BAUDRATE
4.9.4
SER.FORMAT
4.10
CALIB I
4.10.1
I 1 5 mA
4.10.2
I 1 18 mA
4.10.3
I 2 5 mA
4.10.4
I 2 18 mA
4.10.5
I 3 5 mA
4.10.6
I 3 18 mA
Description and settings
Submenu 4.8 System control
Function for system control
* OFF (System control inactive)
* FLOW = 0 (Mass flow readings forced to zero, totaliser frozen)
* FLOW = 0/RST. (Mass flow readings forced to zero, totaliser frozen while active
but reset to zero as condition becomes inactive. Not available with Custody
Transfer Protection)
* OUTPUTS.OFF (Forces all outputs to their OFF states)
Condition for triggering the above function
* DENSITY (Function is triggered if density goes outside Max or Min limits as set in
Fcts 4.8.3 and 4.8.4)
* TEMPERATUR (Function is triggered if temperature goes outside Max or Min
limits as set in Fct 4.8.3 and 4.8.4).
Function not available with Custody Transfer Protection.
Minimum allowable value of temperature or density selected in Fct. 4.8.2
Units: depend on function but will correspond to those set in Fct. 3.2.6 and 3.2.7
Function not available with Custody Transfer Protection.
Maximum allowable value of temperature or density selected in Fct.4.8.2
Units: depend on function but will correspond to those set in Fct. 3.2.6 and 3.2.7
Function not available with Custody Transfer Protection
Submenu 4.9 Communication modules
Display of communication protocol fitted
(OFF, SERIAL, HART, MODBUS, PROFIBUS, FF BUS or KROHNE)
Address
(not available for selection OFF and SERIAL in Fct. 4.9.1)
Setting Baudrate (for option MODBUS in Fct. 4.9.1 only)
Serial format (for option MODBUS in Fct. 4.9.1 only)
Submenu 4.10 Calibration current output 1
Calibration of the current output 1 for 5 mA
Calibration of the current output 1 for 18 mA
see I 1 5 mA
see I 1 18 mA
see I 1 5 mA
see I 1 18 mA
Installation and Operating Instructions OPTIMASS
65

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents