KROHNE OPTIMASS 6400 Supplementary Instructions Manual

KROHNE OPTIMASS 6400 Supplementary Instructions Manual

Coriolis mass flowmeter

Advertisement

OPTIMASS 6400
OPTIMASS 6400
OPTIMASS 6400
OPTIMASS 6400
Coriolis mass flowmeter
Safety manual
Safety manual
Safety manual
Safety manual
© KROHNE 11/2017 - 4004960802 - AD OPTIMASS 6400 SIL R02 en
Supplementary Instructions
Supplementary Instructions
Supplementary Instructions
Supplementary Instructions

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the OPTIMASS 6400 and is the answer not in the manual?

Questions and answers

Robin
January 27, 2025

Hi, do you have a reckomended calibration interval for the 6400F? When to calibrate by manufacturer, or is it maintenanacefree?

1 comments:
Mr. Anderson
February 10, 2025

The KROHNE OPTIMASS 6400 requires calibration during every proof test or safe configuration. A zero calibration is recommended during these procedures, and factory calibration is used in safe operation. The device is not explicitly stated to be maintenance-free, as it requires periodic proof tests, inspections, and calibrations to ensure proper functioning.

This answer is automatically generated

Summary of Contents for KROHNE OPTIMASS 6400

  • Page 1 OPTIMASS 6400 OPTIMASS 6400 OPTIMASS 6400 OPTIMASS 6400 Supplementary Instructions Supplementary Instructions Supplementary Instructions Supplementary Instructions Coriolis mass flowmeter Safety manual Safety manual Safety manual Safety manual © KROHNE 11/2017 - 4004960802 - AD OPTIMASS 6400 SIL R02 en...
  • Page 2: Table Of Contents

    5 Service 5.1 Periodic maintenance..................... 17 5.2 Keep the device clean..................... 17 5.3 Spare parts availability....................17 5.4 Proof test ........................17 5.5 Calibration procedure ....................18 5.6 Troubleshooting......................18 www.krohne.com 11/2017 - 4004960802 - AD OPTIMASS 6400 SIL R02 en...
  • Page 3 CONTENTS OPTIMASS 6400 6 Technical data 6.1 SIL certificate........................19 6.2 Declaration ........................20 6.3 Safety-related characteristics ..................21 7 Notes 11/2017 - 4004960802 - AD OPTIMASS 6400 SIL R02 en www.krohne.com...
  • Page 4: Introduction

    AD OPTIMASS 6400 SIL R02 en 1 Not safety relevant change 1.3 Device description The OPTIMASS 6400 is a 4-wire Coriolis mass flowmeter measuring mass flow rate, total mass, density, temperature, volume flow rate, flow velocity, total volume and concentration of liquids and gases.
  • Page 5: Device Variants

    • I/O option 2 and 3 are intrinsic safe I/Os • Details of the CG number decoding are provided in the handbook [N2]. • The current output at terminal C is the safety relevant output for "Safe Operation". 11/2017 - 4004960802 - AD OPTIMASS 6400 SIL R02 en www.krohne.com...
  • Page 6: Flow Sensor

    Customer specific Customer specific Customer specific Signal converter type Signal converter type Signal converter type Signal converter type 6 or 7 Destination Spare Spare -: all variants are valid www.krohne.com 11/2017 - 4004960802 - AD OPTIMASS 6400 SIL R02 en...
  • Page 7: Related Documentation

    "Complex" system (all failure modes are not well defined). For more data, refer to subsection 7.4.3.1.2 of IEC 61508-2. Proof Test Interval Proof 1oo1 1 out of 1 channel architecture (single channel architecture performs the safety function) 11/2017 - 4004960802 - AD OPTIMASS 6400 SIL R02 en www.krohne.com...
  • Page 8: Specification Of The Safety Function

    A random fault can cause an error of up to 2% of the present measurement value or output current before it is signalled. www.krohne.com 11/2017 - 4004960802 - AD OPTIMASS 6400 SIL R02 en...
  • Page 9: Installation

    It is necessary to use a power supply with voltage limitation or voltage monitoring. 11/2017 - 4004960802 - AD OPTIMASS 6400 SIL R02 en www.krohne.com...
  • Page 10: Operation

    Safe operation Device performs the safe Measurement signal or failure signal measurement according to its configuration and all safety relevant parameters are locked. www.krohne.com 11/2017 - 4004960802 - AD OPTIMASS 6400 SIL R02 en...
  • Page 11: Switch To Safe Operation

    Pressure Suppression disabled Density Mode process Sensor Low Flow Cutoff factory setting (0.2% of nom. mass flow) Process Noise Damping 1.0 s Flow Offset 0 kg/s Flow Correction 11/2017 - 4004960802 - AD OPTIMASS 6400 SIL R02 en www.krohne.com...
  • Page 12 Hardware configuration of safe current output: active Passive or passive (only displayed in non-Ex i version) Flow Direction Forwards Definition of sign of flow value Backwards Zero Calibration Set by zero calibration procedure www.krohne.com 11/2017 - 4004960802 - AD OPTIMASS 6400 SIL R02 en...
  • Page 13: Safe Parameter Verification

    If the verification process is performed via HART make sure that the correct device is addressed by checking the device tag. Please make sure that the device tag is unique. 11/2017 - 4004960802 - AD OPTIMASS 6400 SIL R02 en www.krohne.com...
  • Page 14: Confirmation

    Device is in safe operation or non-SIL operation. INFORMATION! All safety relevant parameters are locked during safe operation. If not safety relevant parameters shall be locked please set the operator password ([N2]). www.krohne.com 11/2017 - 4004960802 - AD OPTIMASS 6400 SIL R02 en...
  • Page 15: Unlock Of Device

    (≤ 3.6 mA). Thus, the output signal for the safe state is less than 3.6 mA. WARNING! If the device is used in a safety loop both the high and low failure current must be monitored. 11/2017 - 4004960802 - AD OPTIMASS 6400 SIL R02 en www.krohne.com...
  • Page 16: Device Failures

    Flow sensor is defect. Replace flow sensor. Temp. Or Strain Res. Def. Hardware failure in temperature or strain Check cabling in case of remote device or measurement. replace flow sensor. www.krohne.com 11/2017 - 4004960802 - AD OPTIMASS 6400 SIL R02 en...
  • Page 17: Service

    Check mass flow measurement accuracy with a calibration rig with at least at 2 measuring points or return the device to the manufacturer for recalibration. The measurement uncertainty must not exceed the maximum error specified in the handbook. Set the device to safe operation. 11/2017 - 4004960802 - AD OPTIMASS 6400 SIL R02 en www.krohne.com...
  • Page 18: Calibration Procedure

    Proof Test Coverage for steps 1-3 (partial proof test): 82% Proof Test Coverage for steps 1-4 (full proof test): 97% KROHNE OPTICHECK can be used to perform the tests 1-3 in a simple way. WARNING! Perform an optical inspection of the sealings, containment, housing and electrical wiring within every proof test.
  • Page 19: Technical Data

    TECHNICAL DATA OPTIMASS 6400 6.1 SIL certificate 11/2017 - 4004960802 - AD OPTIMASS 6400 SIL R02 en www.krohne.com...
  • Page 20: Declaration

    TECHNICAL DATA OPTIMASS 6400 6.2 Declaration www.krohne.com 11/2017 - 4004960802 - AD OPTIMASS 6400 SIL R02 en...
  • Page 21: Safety-Related Characteristics

    IEC 61508-2, section 7.4.9.5 note 3. The useful lifetime can only be extended under responsibility of the plant operator regarding special operation conditions and the employment of suitable intervals for testing and maintenance. 11/2017 - 4004960802 - AD OPTIMASS 6400 SIL R02 en www.krohne.com...
  • Page 22: Notes

    NOTES OPTIMASS 6400 www.krohne.com 11/2017 - 4004960802 - AD OPTIMASS 6400 SIL R02 en...
  • Page 23 NOTES OPTIMASS 6400 11/2017 - 4004960802 - AD OPTIMASS 6400 SIL R02 en www.krohne.com...
  • Page 24 • Process Analysis • Services Head Office KROHNE Messtechnik GmbH Ludwig-Krohne-Str. 5 47058 Duisburg (Germany) Tel.: +49 203 301 0 Fax: +49 203 301 10389 info@krohne.com The current list of all KROHNE contacts and addresses can be found at: www.krohne.com...