MTU 20 V 4000 G23 Technical Publication page 93

Hide thumbs Also See for 20 V 4000 G23:
Table of Contents

Advertisement

88
Fault
code No.
Designation
401
AL Open Load Digital
Input 2
402
AL Open Load Digital
Input 3
403
AL Open Load Digital
Input 4
404
AL Open Load Digital
Input 5
405
AL Open Load Digital
Input 6
406
AL Open Load Digital
Input 7
407
AL Open Load Digital
Input 8
408
AL Open Load Emerg.
Stop Input ESI
410
LO U-PDU
411
LOLO U-PDU
M015715/00E 06-08
Meaning
Alarm configuration; Line
disruption on digital input 2;
Cabling faulty or no resistance
over switch.
Alarm configuration; Line
disruption on digital input 3;
Cabling faulty or no resistance
over switch.
Alarm configuration; Line
disruption on digital input 4;
Cabling faulty or no resistance
over switch.
Alarm configuration; Line
disruption on digital input 5;
Cabling faulty or no resistance
over switch.
Alarm configuration; Line
disruption on digital input 6;
Cabling faulty or no resistance
over switch.
Alarm configuration; Line
disruption on digital input 7;
Cabling faulty or no resistance
over switch.
Alarm configuration; Line
disruption on digital input 8;
Cabling faulty or no resistance
over switch.
Alarm configuration; Line
disruption on the input for
emergency stop; Cabling faulty
or no resistance over switch.
Alarm configuration limit
value 1; Preliminary warning:
Injector voltage too low.
Alarm configuration limit value
2; Main warning: Injector
voltage too low.
Task
1. Check cabling
2. Check input of
target device.
3. Contact
Service.
1. Check cabling
2. Check input of
target device.
3. Contact
Service.
1. Check cabling
2. Check input of
target device.
3. Contact
Service.
1. Check cabling
2. Check input of
target device.
3. Contact
Service.
1. Check cabling
2. Check input of
target device.
3. Contact
Service.
1. Check cabling
2. Check input of
target device.
3. Contact
Service.
1. Check cabling
2. Check input of
target device.
3. Contact
Service.
1. Check cabling
2. Check input of
target device.
3. Contact
Service.
1. Check cabling.
2. Check power
supply.
3. Contact
Service.
1. Check cabling
2. Check power
supply.
3. Contact
Service.
Troubleshooting
Related
parameter No.
2.8006.626
2.8006.627
2.8006.628
2.8006.629
2.8006.630
2.8006.631
2.8006.632
2.8006.633
2.0141.921
2.0141.922
© MTU