Outlet Configurations; Printer Outlet Voltages-60 Hz - Xerox DocuPrint 180 NPS Installation Planning Manual

Docuprint network printer series
Hide thumbs Also See for DocuPrint 180 NPS:
Table of Contents

Advertisement

PRINTER SPECIFICATIONS AND REQUIREMENTS

Outlet configurations

Printer outlet voltages—60 Hz
Service outlet
configuration
4 Wire
4 Wire
4 Wire
4 Wire
4 Wire
6-2
XEROX DOCUPRINT NETWORK PRINTER SERIES INSTALLATION PLANNING GUIDE FOR MODELS 96/4635/180 NPS
This section discusses specifications for system outlets and the
required wall outlet configurations for the USA / Canada and
internationally.
Note: All power outlets must be dedicated to this equipment. When
determining the electrical connections for your printer, make sure
that:
Each power cord has a separate circuit
The printer power cord configurations match your receptacle
Your electrical outlets are within the required specifications.
50 Hz systems: Ensure that power connections are per local codes/
regulations.
The following table shows the voltages for the outlets on your printing
system. All power outlets must have a dedicated circuit for each
system equipment piece. Make sure each power cord has a separate
circuit.
Table 6-2.Printer (60 Hz) voltage requirements at power outlet
Measurement of wiring
Line 1 to neutral
Line 2 to neutral
Neutral to ground
Line 1 to line 2
Line 1 to line 2
Nominal
Range
120 V RMS
107-127 V RMS
120 V RMS
107-127 V RMS
0
0-10 V RMS
208 V RMS
182-220 V RMS
240 V RMS
210-254 V RMS