PRINTER SPECIFICATIONS AND REQUIREMENTS
Printer outlet voltages—50 Hz
DELTA configurations—50 Hz
WYE (or Star) configurations—50 Hz
Service outlet
configuration
5 Wire 415 V
5 Wire 415 V
5 Wire 415 V
5 Wire 415 V
5 Wire 415 V
5 Wire 415 V
6-4
XEROX DOCUPRINT NETWORK PRINTER SERIES INSTALLATION PLANNING GUIDE FOR MODELS 96/4635/180 NPS
All power outlets must have a dedicated circuit for each system
equipment piece. Make sure each power cord has a separate circuit.
Note: Consult with your service representative to determine the
type of plug and receptacle to be used for your 50 Hz system.
For 50 Hz DELTA configurations, measure the DELTA connection
voltages at the power source.
Table 6-3.Printer (50 Hz) DELTA voltage
Service outlet
configuration
Measurement
4 Wire 220 V
Line 1 to line 2
4 Wire 220 V
Line 2 to line 3
4 Wire 220 V
Line 1 to line 3
4 Wire 230 V
Line 1 to line 2
4 Wire 230 V
Line 2 to line 3
4 Wire 230 V
Line 1 to line 3
5 Wire 240 V
Line 1 to line 2
5 Wire 240 V
Line 2 to line 3
5 Wire 240 V
Line 1 to line 3
For the 50 Hz WYE configuration, measure the WYE or Star
connection voltages at the power source.
Table 6-4.Printer (50 Hz) WYE (Star) 415 voltage
Measurement
Line 1 to line 2
Line 2 to line 3
Line 1 to line 3
Line 1 to neutral
Line 2 to neutral
Line 3 to neutral
Nominal
Range
220 V RMS
198-242 V RMS
220 V RMS
198-242 V RMS
220 V RMS
198-242 V RMS
230 V RMS
207-253 V RMS
230 V RMS
207-253 V RMS
230 V RMS
207-253 V RMS
240 V RMS
216-264 V RMS
240 V RMS
216-264 V RMS
240 V RMS
216-264 V RMS
Nominal
Range
415 V RMS
374-457 V RMS
415 V RMS
374-457 V RMS
415 V RMS
374-457 V RMS
240 V RMS
216-264 V RMS
240 V RMS
216-264 V RMS
240 V RMS
216-264 V RMS