Figure 28, Selling Power Stored In The Batteries; Hypothetical Time Of Day Operational History - Xantrex SW Series Owner's Manual

Sw series inverter/chargers
Table of Contents

Advertisement

OPERATION
SELLING POWER - STORED IN THE BATTERIES
Power stored in the batteries can also be sold into the utility grid. This can be used together with the solar
array or alone without a solar array. The inverter can be programmed to sell the energy in the batteries at
a specific time and then to recharge the batteries at another time. Both the discharge level and discharge
rate can be adjusted to control the battery selling process.
Selling the power stored in the batteries can be used to level the output of the combined solar array and
battery system. This is beneficial during conditions of cloudy weather when the solar array output will vary
with each cloud that passes over. To set-up this ability, adjust the SET BATTERY SELL VOLTS DC menu
item under the BATTERY SELLING (17) menu heading for the maximum discharge voltage level
acceptable. The SET MAX SELL AMPS AC menu item should be set for the expected maximum output of
the solar array. Next, access the GRID USAGE TIMER (18) menu heading to allow setting of the time
period that the battery will be allowed to recharge during by adjusting the SET START CHARGE TIME and
SET END CHARGE TIME menu items. Outside of this time period, the inverter will sell the power stored in
the battery to the utility grid until the voltage reaches the BATTERY SELL VOLTS DC setting.
This mode can use the battery to maximize the output of the system during a specific period of time. An
example of these setting follows:
Begin Day
00:00
Time
Float Volts
DC Setting
Set Float
Volts DC
Charging from the
DC source (wind,
hydro or solar) has
started.
POSITIVE (+) = Inverter is drawing power from grid.
NEGATIVE (-) = Inverter is selling power to grid.
Input
amps AC
00
{
AC amps to grid (-)
{
AC amps from grid (+)
LEGEND
Display/Settings
on Control Panel
Information

Figure 28, Selling Power Stored In The Batteries; Hypothetical Time Of Day Operational History

2001 Xantrex Technology, Inc.
Page
5916 - 195th Street N. E.
86
Arlington, WA 98223
Battery charging
08:00
from grid has
stopped
End charge
time
08:00
Battery Sell Volts
Set Float
Volts DC
13.4
Set Battery Sell
DC Volts
13.4
Volts DC
AC amps
Battery charging
10:00
from grid has
started
Start charge
time
18:00
Bulk Volts
DC Setting
DC Setting
Set Bulk Volts
DC
14.4
12.4
Max Sell
Amps Setting
Set Max Sell
amps
30
Telephone: 360/435-8826
Fax: 360/435-2229
www.traceengineering.com
End Day
18:00
20:00
23:59
Bulk charging
has started
Set Start Bulk
time
20:00
Set Absorption
time h: m
2:00
Absorption Time
Max Charge
Amps Setting
Set Max Charge
amps AC
30
SW Series Inverter/Charger
Part No. 2031-5
Rev. C: February 2001