TECHNICAL INFORMATION
SETUP MENU – 12 VDC (120 VAC/60HZ) MODELS
To access the SETUP MENU, press the RED and GREEN buttons on your CONTROL PANEL (or
SWRC) at the same time. To exit the Setup Menu, press the ON/OFF MENU button or use the down
MENU HEADING button until you reach the USER MENU (menu headings 1 – 8)
MENU HEADING
Inverter Setup
Battery Charging
AC Inputs
Gen Auto Start Setup
Gen Starting Details
Auxiliary Relays R9 R10
Bulk Charge Trigger Timer
Low Battery Transfer (LBX) 16 Set Low Battery transfer VDC
Battery Selling
Grid Usage Timer
2001 Xantrex Technology, Inc.
Page
5916 - 195th Street N. E.
124
Arlington, WA 98223
MENU ITEM
9 Set Grid Usage
Set Low Battery cut out VDC
Set LBCO delay minutes
Set Low battery cut in VDC
Set High battery Cut Out VDC
Set search watts
Set search spacing
10 Set Bulk volts DC
Set Absorption time h:m
Set Float volts DC
Set Equalize volts DC
Set Equalize time h:m
Set Max Charge amps AC
Set Temp Comp
11 Set Grid (AC1) amps AC
Set Gen (AC2) amps AC
Set Input lower limit VAC
Set Input upper limit VAC
12 Set Load Start amps AC
Set Load Start delay min
Set Load Stop delay min
Set 24 hr start volts DC
Set 2 hr start volts DC
Set 15 min start volts DC
Read LBCO 30 sec start VDC
Set Exercise period days
Set Maximum run time h:m
13 Set RY7 Function
Set Gen warmup seconds
Set Pre Crank seconds
Set Max Cranking seconds
Set Post Crank seconds
14 Set Relay 9 volts DC
R9 Hysteresis volts DC
Set Relay 10 volts DC
R10 Hysteresis volts DC
Set Relay 11 volts DC
R11 Hysteresis volts DC
15 Start Bulk Time H:M
Set Low Battery cut in VDC
17 Set Battery Sell volts DC
Set Max Sell amps AC
18 Set Start Charge time h:m
End Stop Charge time h:m
SELECTION
DEFAULT
RANGE
SETTINGS
FLT SELL SLT LBX
0.80 – 25.5
00 - 255
00.0 – 16.5
00.0 – 16.5
00 - 240
00 – 255
10.0 – 16.0
00:00 – 23:50
10.0 – 16.0
10.0 – 16.0
00:00 – 23:50
01 - 25
LeadAcid Nicad
00 - 63
00 - 63
80 - 111
128 - 149
00 - 63
00.0 – 25.5
00.0 – 25.5
05.0 – 25.5
05.0 – 16.5
05.0 – 16.5
05.0 – 16.5
00 - 255
00:00 – 23:50
GlowStop Run
16 - 255
00 - 255
01 - 15
00 - 255
00.0 – 16.5
00.1 – 12.8
00.0 – 16.5
00.1 – 12.8
00.0 – 16.5
00.1 – 12.8
00:00 – 23:50
05.0 – 16.5
05.0 – 16.5
10.0 – 16.0
01 - 25
00:00 – 23:50
00:00 – 23:50
Telephone: 360/435-8826
Fax: 360/435-2229
www.traceengineering.com
.
USER
SETTINGS
FLT
11.0
15
13.0
16.0
48
59
14.4
02:00
13.4
14.4
02:00
20
LeadAcid
60
30
108
132
33
05.0
05.0
12.3
11.8
11.3
11.0
30
08:00
Run
60
10
10
30
14.5
01.0
14.8
01.0
15.0
01.0
00:00
11.3
13.0
13.4
30
21:00
21:00
SW Series Inverter/Charger
Part No. 2031-5
Rev. C: February 2001