GEN AUTO START SETUP (12) MENU HEADING
Set Load Start
amps AC
33
All models
Range: 00 to 63
Sets the AC load current that will initiate the automatic generator control system when the current remains
above this setting continuously for the LOAD START DELAY MIN period.
Set Load Start
delay min
05.0
All models
Range: 00.0 to 25.5
Sets the time delay period that will initiate automatic generator control system when the current remains
above the LOAD START AMPS AC setting continuously for this time period.
Set Load Stop
delays min
05.0
All models
Range: 00.0 to 25.5
Sets the amount of time that the automatic generator will continue to run after the load current
(determined by the LOAD AMPS AC meter) decreases below the LOAD START AMPS AC setting.
Set 24 hr start
volts DC
12.3
12 VDC models
Range: 05.0 to 16.5
Sets the battery voltage that will initiate the automatic generator control system if the voltage remains
below this setting continuously for 24 hours. This setting is not temperature compensated. This 24-hour
start is defeated if the QUIET TIME under GENERATOR TIMER (7) is enabled.
Set 2 hr start
volts DC
11.8
12 VDC models
Range: 05.0 to 16.5
Sets the battery voltage that will initiate the automatic generator control system if the voltage remains
below this setting continuously for 2 hours. This setting is not temperature compensated. This 2-hour start
is defeated if the QUIET TIME under GENERATOR TIMER (7) is enabled.
Set 15 min start
volts DC
11.3
12 VDC models
Range: 05.0 to 16.5
Sets the battery voltage that will initiate the automatic generator control system if the voltage remains
below this setting continuously for 15 minutes. This setting is not temperature compensated. This 15-
minute start is defeated if the QUIET TIME under GENERATOR TIMER (7) is enabled.
Read 30 sec LBCO
start VDC
11.0
12 VDC models
Range: 05.0 to 16.5
Displays the battery voltage setting that will initiate the automatic generator control system if the voltage
remains below the setting continuously for 30 seconds. This setting is not temperature compensated. This
display is linked and is adjusted by the SET LOW BATTERY CUT OUT VDC menu item setting under the
INVERTER SETUP (9) menu heading. This 30-second start will attempt to start the auto start generator
even if the QUIET TIME under GENERATOR TIMER (7) is enabled.
2001 Xantrex Technology, Inc.
5916 - 195th Street N. E.
Arlington, WA 98223
Set 24 hr start
volts DC
24.6
24 VDC models
Range: 10.0 to 35.5
Set 2 hr start
volts DC
23.6
24 VDC models
Range: 10.0 to 35.5
Set 15 min start
volts DC
22.6
24 VDC models
Range: 10.0 to 35.5
Read 30 sec LBCO
start VDC
22.0
24 VDC models
Range: 10.0 to 35.5
Telephone: 360/435-8826
Fax: 360/435-2229
www.traceengineering.com
Set 24 hr start
volts DC
49.2
48 VDC models
Range: 20.0 to 71.0
Set 2 hr start
volts DC
47.2
48 VDC models
Range: 20.0 to 71.0
Set 15 min start
volts DC
45.2
48 VDC models
Range: 20.0 to 71.0
Read 30 sec LBCO
start VDC
44.0
48 VDC models
Range: 20.0 to 71.0