Output A and B as pulse volume
MAG 8000
When output A or B is configured as volume per pulse, the output delivers a pulse when the
preset volume based on either Forward/Reverse or Net Forward/Net Reverse flow has passed
the sensor in the selected direction. The volume per pulse is freely scalable, from 0.000001 to
10 000 units per pulse, and should not exceed the pulse rate of the output configuration table.
MAG 8000 CT
The volume per pulse is defined in the MAG 8000 CT version to 0.001 or 0.01 or 0.1 or 1 m
pulse.
Output B as alarm output
MAG 8000
When output B is configured as an "alarm" output, it will follow the internal alarms that were
previously chosen in the Alarm Configuration List (Page 53).
Note
Alarm output is inverted to a pulse output providing an alarm if power disappears or cable
connection is interrupted.
SITRANS FM MAG 8000
Operating Instructions, 03/2020, A5E03071515-AH
Forward
Reverse
Cut-off
Alarm output
Alarm status
On - Off
No Error
PR
Pulse rate
PF
Pulse frequency
PW
Pulse width
Technical data
10.6 Output characteristics