C2 Off Delay: Compressor 2 will continue to run for this amount of time before turning
off, with other conditions applied. Default value is 5 seconds, and selectable from 0 to
999 seconds.
Move the cursor to the title block by pressing the ENTER key stepping through all the
inputs. To return to the main Menu press the ESC key or to view the following screen
press the DOWN key.
The Reheat Settings screen will be displayed (values are for reference only):
Reheat Stages: There is only one stage maximum for GIAX units. There are 3 choices
 1-Elect: Reheat only comes ON in dehumidification mode (factory default)
 One: Reheat comes on in dehumidification mode and when temperature goes
below cooling setpoint minus deadband
 None: Reheat is not available. In this case, dehumidification will not be available.
Enable SCR Y4: Allows Enable/Disable of the SCR control to modulate the reheat.
Optional SCR hardware is required.
Move the cursor to the title block by pressing the ENTER key stepping through all the
inputs. To return to the main Menu press the ESC key or to view the following screen
press the DOWN key.
10-2014
gForce User Manual ● 83