Data Aire gForce Ultra User Manual page 77

Dx, single and dual circuit 36, 45, 56, 70 and 106 kw
Table of Contents

Advertisement

CW Mode: This is the fan control settings for the unit when a chilled water valve is
used. There are 6 different modes.
DX Mode: This is the fan control settings for the unit when a compressor runs. There
are 6 different modes:
 Const Speed: See section 9.1.6.
 BMS Speed: See section 9.1.5.
 Mod to Rack: See section 9.1.1.
 Mod to RetT: See section 9.1.3.
 Mod to Comp: See section 9.1.2.
Move the cursor to the title block by pressing the ENTER key stepping through all the
inputs. To return to the main Menu press the ESC key or to view the following screen
press the DOWN key.
The Fan Range Settings screen will be displayed only if the fan speed from the
screen above was not in "Constant" mode (values are for reference only):
10-2014
gForce User Manual ● 77