The following steps indicate how to use the dap4™ controller to adjust the plug fan
speed to temporarily reduce the plug fan current to set the current sensing relay.
Press the MENU key and enter either Service or Factory Level password. Go to Menu I:
Manual Control
Adjust the "Return to Auto" to 300 seconds. This will allow time to operate the plug
fan(s) at a lower speed to make the current sensing relay adjustment before returning
the unit back to the original speed.