Flowserve LTQ008 Series User Instructions page 41

Single-phase and low voltage products, compact quarter-turn electric actuator
Table of Contents

Advertisement

LTQ008 – LTQ230 Series Single-Phase Products User Instructions –
Table 4: Fault symptoms for failsafe control models
A c t u a t o r d o e s n o t m o v e t o e x p e c t e d F a i l - S a f e p o s i t i o n u p o n l o s s o f m a i n s p o w e r
 A c t u a t o r d o e s n o t c o m p l e t e t h e m o v e t o t h e f u l l e n d o f t r a v e l p o s i t i o n u p o n l o s s o f m a i n s
Stored Energy device not connected
Stored Energy device not charged
Fail-Safe direction incorrectly set
Stored Energy device not sufficiently
charged
Fault OUT contact is closed. ERR indicator
on PCB is ON
ERR indicator is ON
Target
After actuator commissioning, plug the two-pin green
connectors together. The BAT status LED must be ON when power
is On.
Unit must charge for at least twelve hours after initial
connection is made
Reset 4 position DIP Switch
Unit must charge for at least twelve hours after initial
connection is made.
Yellow BAT status indicator must be on or flashing when mains
power is ON and stored energy device is plugged into connector.
Motor current draw exceeds the capacity of the stored energy
device. Check valve torque and charge time.
Mains power ON time is insufficient between power failures -
increase ON time.
Stored energy demand cycle has depleted the life of the device
- replace stored energy pack.
Stored energy device disconnected - reconnect two-pin plug.
Stored energy device voltage drops below 18.5VDC.
Page 40 of 47
AIIOM000164
Action
EN

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ltq230 seriesLtq008Ltq017Ltq034Ltq070Ltq088 ... Show all

Table of Contents