Pilz PSS u2 ES 8DI Operating Manual
Pilz PSS u2 ES 8DI Operating Manual

Pilz PSS u2 ES 8DI Operating Manual

Control system / remote i/o system

Advertisement

Quick Links

PSS u2 ES 8DI
Control system PSS u2
}
Remote I/O system PSS u2
}
Operating Manual-1003610-EN-01

Advertisement

Table of Contents
loading

Summary of Contents for Pilz PSS u2 ES 8DI

  • Page 1 PSS u2 ES 8DI Control system PSS u2 Remote I/O system PSS u2 Operating Manual-1003610-EN-01...
  • Page 2 Preface This document is a translation of the original document. All rights to this documentation are reserved by Pilz GmbH & Co. KG. Copies may be made for internal purposes. Suggestions and comments for improving this documentation will be gratefully received.
  • Page 3: Table Of Contents

    Section 7 Wiring General wiring guidelines 7.1.1 Connection mechanism for terminal blocks Terminal configuration Section 8 Operation Display elements and messages Section 9 Technical details Section 10 Order reference 10.1 Product 10.2 Accessories Operating Manual PSS u2 ES 8DI 1003610-EN-01...
  • Page 4: Operating Manual Pss U2 Es 8Di

    This operating manual explains the function and operation, describes the installation and provides guidelines on how to connect the product. This documentation is valid for the product PSS u2 ES 8DI. It is valid until new documenta- tion is published.
  • Page 5 Introduction INFORMATION This gives advice on applications and provides information on special fea- tures. Operating Manual PSS u2 ES 8DI 1003610-EN-01...
  • Page 6: Overview

    Details of the terminal blocks that can be used are available under "Intended Use". Module features Using the product PSS u2 ES 8DI: Electronic module with digital inputs for standard applications The product has the following features: 8 type 3 digital inputs in accordance with IEC 61131-2 Configurable input filter time: 0 …...
  • Page 7: Safety

    Use of the module outside the areas described in this manual, Any use of the module that is not in accordance with the technical details. The module PSS u2 ES 8DI may be used in conjunction with the following terminal block: 8-pin terminal block...
  • Page 8: Warranty And Liability

    Any type of modification has been made (e.g. exchanging components on the PCB boards, soldering work etc.). 3.3.3 Disposal When decommissioning, please comply with local regulations regarding the disposal of electronic devices (e.g. Electrical and Electronic Equipment Act). Operating Manual PSS u2 ES 8DI 1003610-EN-01...
  • Page 9: Function Description

    Data (ST) Periphery Supply +24 V DC Fig.: Block diagram PSS u2 ES 8DI Supply The module supply provides the module with voltage. Inputs The status of the inputs is signalled to the head module via the module bus. The inputs are fitted with a configurable software filter.
  • Page 10 If the signal is longer than the pulse stretch time, then it is not stretched stretch. any further. Signal requirements at the terminals: The 0-signal and the subsequent 1-signal together must be present at the input for longer than twice the configured pulse stretch time t stretch Operating Manual PSS u2 ES 8DI 1003610-EN-01...
  • Page 11 Duration of pulse stretching stretch Time for which a signal must be present at the input in order to be de- signal_min tected Stretched 1-signal in the module TRUE Stretched 0-signal in the module FALSE Operating Manual PSS u2 ES 8DI 1003610-EN-01...
  • Page 12 Stretched 1-signal in the module TRUE Stretched 0-signal in the module FALSE Clamp 1-signal 0-signal Pulse stretching stretch stretch Stretched signal signal_min signal_min TRUE FALSE Fig.: Timing diagram: pulse stretching with variable signal duration Operating Manual PSS u2 ES 8DI 1003610-EN-01...
  • Page 13: Reaction Times

    – Switching off the LEDs to display the module and terminal status Standby mode – All module functions are inactive. – The LEDs for displaying the module and terminal status are switched off. Operating Manual PSS u2 ES 8DI 1003610-EN-01...
  • Page 14: Address Assignment

    Input data I1 Bit 2 Input data I2 Bit 3 Input data I3 Bit 4 Input data I4 Bit 5 Input data I5 Bit 6 Input data I6 Bit 7 Input data I7 Operating Manual PSS u2 ES 8DI 1003610-EN-01...
  • Page 15: Installation

    6.1.1 Dimensions The dimensions include the backplane, electronic module and terminal block. 12,5 51,1 111,1 Fig.: Dimensions in mm, including backplane, electronic module and terminal block Operating Manual PSS u2 ES 8DI 1003610-EN-01...
  • Page 16: Inserting And Removing An Electronic Module

    The mechanics of the electronic modules are designed for 20 plug in/out cycles. 6.2.1 Inserting an electronic module 1. Insert the electronic module into the suspen- sion lug on the back- plane 2. Press the electronic module downwards until you hear it click into place. Operating Manual PSS u2 ES 8DI 1003610-EN-01...
  • Page 17 Installation 3. Insert the terminal block into the suspen- sion lug on the module. 4. Press the terminal block downwards until you hear it click into place. Operating Manual PSS u2 ES 8DI 1003610-EN-01...
  • Page 18: Removing An Electronic Module

    A new electronic module can be inserted during operation. Effects: Module bus communication between the other modules is not interrupted. The head module may need to be configured and restarted in order for the new module to be detected. Operating Manual PSS u2 ES 8DI 1003610-EN-01...
  • Page 19: Wiring

    The minimum cable cross section for field connection terminals on the terminal blocks is 0.15 mm (AWG26). The maximum cable cross section for field connection terminals on the terminal blocks is 1.5 mm with ferrules (AWG14) Use copper wiring. Operating Manual PSS u2 ES 8DI 1003610-EN-01...
  • Page 20: Terminal Configuration

    PSS u2 ES 8PTD 24V 0V 5: Input I2 ES 8DI ES 8PTD 24V 0V 7: Input I3 9: Input I4 11: Input I5 13: Input I6 15: Input I7 24 V Operating Manual PSS u2 ES 8DI 1003610-EN-01...
  • Page 21: Operation

    Green The module status display and all See module's terminal status displays flash simul- diagnostic log. taneously Periphery supply is missing/temper- ature error: Too hot (1) ) There are two levels of overtemperature. Operating Manual PSS u2 ES 8DI 1003610-EN-01...
  • Page 22 After the "too hot" message has been received, if the temperature drops back below the "too warm" threshold value, the module will switch to an error-free state. Legend LED on LED flashes LED flashes briefly LED off Operating Manual PSS u2 ES 8DI 1003610-EN-01...
  • Page 23: Technical Details

    Climatic suitability EN 60068-2-78 In accordance with the standard Humidity 93 % r. h. at 40 °C Condensation during operation Not permitted 2000 m Max. operating height above sea level EN 61131-2 (Zone B) Operating Manual PSS u2 ES 8DI 1003610-EN-01...
  • Page 24 Rated surge voltage 2500 V Mechanical data Material Housing Mounting type plug-in Dimensions Height 110,8 mm Width 12,5 mm Depth 72,5 mm Weight 30 g Where standards are undated, the 2015-04 latest editions shall apply. Operating Manual PSS u2 ES 8DI 1003610-EN-01...
  • Page 25: Order Reference

    Coding elements Product type Features Order No. PSS u2 A CE E (10 pc.) Coding elements, 10 pieces 328 860 PSS u2 A CE T (10 pc.) Coding strip, 10 pieces 328 861 Operating Manual PSS u2 ES 8DI 1003610-EN-01...
  • Page 26 Front cover Support Technical support is available from Pilz round the clock. Americas Australia Scandinavia Brazil +61 3 95446300 +45 74436332 +55 11 97569-2804 Spain Canada Europe +34 938497433 +1 888-315-PILZ (315-7459) Austria Switzerland +41 62 88979-30 Mexico +43 1 7986263-0...

This manual is also suitable for:

328 301