Pilz PSSu K S 16DI Operating Manual

Pilz PSSu K S 16DI Operating Manual

Compact module without connector, labelling bracket and labelling strips, base type

Advertisement

Quick Links

PSSu K S 16DI
}
Decentralised system PSSuniversal I/O
Operating Manual-22053-EN-09

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the PSSu K S 16DI and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Pilz PSSu K S 16DI

  • Page 1 PSSu K S 16DI Decentralised system PSSuniversal I/O Operating Manual-22053-EN-09...
  • Page 2 Preface This document is a translation of the original document. All rights to this documentation are reserved by Pilz GmbH & Co. KG. Copies may be made for internal purposes. Suggestions and comments for improving this documentation will be gratefully received.
  • Page 3: Table Of Contents

    Install labelling bracket Section 6 Wiring General wiring guidelines 6.1.1 Connectors' mechanical connection 6.1.2 Connect/disconnect the cables Terminal configuration Connecting the module Section 7 Operation Messages Display elements 7.2.1 Display elements for module diagnostics Operating Manual PSSu K S 16DI 22053-EN-09...
  • Page 4 Contents 7.2.2 Display elements for input status Section 8 Technical details Section 9 Order reference Product Accessories Operating Manual PSSu K S 16DI 22053-EN-09...
  • Page 5: Operating Manual Pssu K S 16Di

    Introduction Introduction Validity of documentation This documentation is valid for the product PSSu K S 16DI. It is valid until new documenta- tion is published. This operating manual explains the function and operation, describes the installation and provides guidelines on how to connect the product.
  • Page 6: Definition Of Symbols

    It also highlights areas within the text that are of particular import- ance. INFORMATION This gives advice on applications and provides information on special fea- tures. Operating Manual PSSu K S 16DI 22053-EN-09...
  • Page 7: Overview

    Module error 2 x 10-pin connector strip Communication via: – Standard fieldbus For standard applications in system environment A and B Accessories: Connector with spring-loaded terminals (necessary for operation) Labelling bracket Labelling strips (sheets) Operating Manual PSSu K S 16DI 22053-EN-09...
  • Page 8: Front View

    3: Connector strip X1 for connectors with spring-loaded terminals 4: Connector strip X2 for connectors with spring-loaded terminals 5: Labelling strip for connector strip X2 6: Labelling strip for connector strip X1 7: LEDs for status display and module diagnostics Operating Manual PSSu K S 16DI 22053-EN-09...
  • Page 9: Safety

    The module may be used for standard applications in system environment A and B. The module PSSu K S 16DI may be used as a safety component in accordance with the Lifts Directive 95/16/EC in accordance with the requirements of EN 81-1/2:1998+A3:2009, EN 81-20:2015, EN 81-50:2015, EN 81-22:2014 and EN 115-1:2008+A1:2010.
  • Page 10: Safety Regulations

    In safety-related applications, please comply with the mission time T in the safety-re- lated characteristic data. When decommissioning, please comply with local regulations regarding the disposal of electronic devices (e.g. Electrical and Electronic Equipment Act). Operating Manual PSSu K S 16DI 22053-EN-09...
  • Page 11: Function Description

    When the PSSu E F PS1(-T) or PSSu E F PS2(-T)(-R) is used to supply the system, the module supply is buffered for 20 ms if the supply voltage is interrupted. The module provides the following diagnostic data: Start-up error Configuration error ST communication error Bus termination error Temperature error Operating Manual PSSu K S 16DI 22053-EN-09...
  • Page 12: Reaction Times

    Data access is via pre-defined I/O data types: I/O data name I/O data type I/O data element Meaning I00 … I07 ST_I_DI Data: BOOL Input data I00 ... I07 O00 … O07 ST_O_DO Data: BOOL Output data O00 ... O07 Operating Manual PSSu K S 16DI 22053-EN-09...
  • Page 13: Installation

    Electrostatic discharge can damage components. Ensure against discharge before touching the product, e.g. by touching an earthed, conductive sur- face or by wearing an earthed armband. 5.1.1 Dimensions Module with connector: 62,7 mm (2.469") 30 mm 49,2 mm (1.181") (1.937") Operating Manual PSSu K S 16DI 22053-EN-09...
  • Page 14 Installation Module with connector and labelling bracket: 30 mm 76,7 mm (1.181") (3.020") Operating Manual PSSu K S 16DI 22053-EN-09...
  • Page 15: Install Compact Module

    – On the mounting rail, carefully slide the compact module to the left, in parallel to the adjoining module, until you hear the lateral mounting hooks on the adjacent module lock into position [4]. Operating Manual PSSu K S 16DI 22053-EN-09...
  • Page 16 Installation Schematic representation: Operating Manual PSSu K S 16DI 22053-EN-09...
  • Page 17: Install/Uninstall Connector

    Schematic representation: Uninstallation procedure: Push both locking levers to the left, as far as they will go [1]. INFORMATION This will automatically lift the connector, which can then be removed from the module. Operating Manual PSSu K S 16DI 22053-EN-09...
  • Page 18 Installation NOTICE As you remove the connector, grasp the connector housing and not the cable harness. Schematic representation: Operating Manual PSSu K S 16DI 22053-EN-09...
  • Page 19: Install Labelling Bracket

    We recommend that the labelling strips are attached to the labelling bracket prior to in- stallation. Slot the two pins on the labelling bracket into the receiving lugs on the module [1]. Check that the labelling bracket is firmly seated. Schematic representation: Operating Manual PSSu K S 16DI 22053-EN-09...
  • Page 20: Wiring

    Check that the cable is firmly seated [3]. Disconnect cable: Using the screwdriver, press the actuator button down as far as it will go [4], keep it held down and pull the cable out of the plug connection [4]. Operating Manual PSSu K S 16DI 22053-EN-09...
  • Page 21 Wiring Fig.: Connect and disconnect the cables Operating Manual PSSu K S 16DI 22053-EN-09...
  • Page 22: Terminal Configuration

    I 09: Input 9 I 10: Input 10 I 11: Input 11 I 12: Input 12 I 13: Input 13 I 14: Input 14 I 15: Input 15 0 V: 0 V (periphery supply) Operating Manual PSSu K S 16DI 22053-EN-09...
  • Page 23 I 10: Input 10 loaded termin- I 11: Input 11 als. I 12: Input 12 I 13: Input 13 I 14: Input 14 I 15: Input 15 0 V: 0 V (periphery supply) Operating Manual PSSu K S 16DI 22053-EN-09...
  • Page 24: Connecting The Module

    Input circuit PSSu A Con 1/10 C PSSu A Con 3/30 C Single-wire technology 24 V I 02 I 06 24 V Two-wire technology I 02 24 V Three-wire technology 24 V I 02 Operating Manual PSSu K S 16DI 22053-EN-09...
  • Page 25: Operation

    Ensure there is sufficient ventila- Error stack entry tion in the control cabinet or pre- vent overload. Further information on PSSu error messages is available in the online help for the PSSuni- versal Assistant system software. Operating Manual PSSu K S 16DI 22053-EN-09...
  • Page 26: Display Elements

    Each input is assigned an LED for displaying the input status (LEDs “I 00 … I 15”). Meaning Designa- Colour Status Signal tion I 00 - - - 0 signal Green 1 signal I 15 Operating Manual PSSu K S 16DI 22053-EN-09...
  • Page 27: Technical Details

    Potential isolation between input and internal module bus voltage Environmental data Climatic suitability EN 60068-2-1, EN 60068-2-14, EN 60068-2-2, EN 60068-2-30, EN 60068-2-78 Ambient temperature In accordance with the standard EN 60068-2-14 Temperature range 0 - 60 °C Operating Manual PSSu K S 16DI 22053-EN-09...
  • Page 28 Conductor cross section with spring-loaded terminals: Flexible with/without crimp connector 0,2 - 1 mm², 22 - 18 AWG Spring-loaded terminals: Terminal points per connec- tion Stripping length with spring-loaded terminals 8 mm Operating Manual PSSu K S 16DI 22053-EN-09...
  • Page 29 128,9 mm Width 30 mm Depth 56 mm Depth incl. connector (accessories) 69,5 mm Depth incl. labelling bracket (accessories) 83,5 mm Weight 87 g Where standards are undated, the 2005-04 latest editions shall apply. Operating Manual PSSu K S 16DI 22053-EN-09...
  • Page 30: Order Reference

    PSSu A LC 0.1 Labelling bracket, scope of supply: 5 pieces 312 966 PSSu A LA0 Labelling strips, laser printable, scope of supply: 1080 pieces 312 958 (10 x DIN A4 sheet, 108 on each) Operating Manual PSSu K S 16DI 22053-EN-09...
  • Page 31 Front cover Support Technical support is available from Pilz round the clock. Americas Australia Scandinavia Brazil +61 3 95600621 +45 74436332 +55 11 97569-2804 Spain Canada Europe +34 938497433 +1 888-315-PILZ (315-7459) Austria Switzerland Mexico +43 1 7986263-0 +41 62 88979-30...

This manual is also suitable for:

312430

Table of Contents