en | Operation
Notice!
The fire panel test function is designed for operation by a single
person:
The fire panel automatically resets the alarm 15 seconds after
an alarm is triggered in a zone in test mode. This is followed by
the set time for disabling the zone and the stabilization time for
the detectors. The next detector can then be tested.
Removing individual zones from test mode
Access the Zones menu in test mode as described above. Use
the zone keys to cancel test mode for the relevant zones. The
code below the selected zone in the LCD disappears.
Disabling zones
Caution!
Only disable zones for brief periods of time. Disabled zones will
!
not trigger an alarm in the event of a fire.
1
1
ACK
2019.07 | 5.1 | F.01U.172.982
Press the "Test" key and then zone key 3.
3
This takes you to the Dis/Enable submenu
Press zone key 1.
This takes you to the Zones submenu
Select the zones to be disabled. To do so, press the
8
...
relevant zone keys (1 to 8).
A code appears below the selected zone(s) in the
LCD.
Confirm your selection with the ACK key.
The "Disable" LED and the LEDs for the selected
zones are illuminated yellow.
Conventional fire panel
Bosch Sicherheitssysteme GmbH