28
en | Operation
When you disable the relays, a message confirming the
disablement appears on the LCD after exiting the menu.
Re-enabling relays
Go to the Disable Relays menu as described above. You are
prompted to confirm the re-enablement. Press the ACK key. The
relays are re-enabled.
Disabling/enabling All (zones, relays, notification appliances)
4
ACK
You can use the "Enable All" function if only one relay, one zone
or one notification appliance has been disabled.
4.2.3

Menu

In addition to the functions in level 1, the menu provides the
following options:
Displaying the configuration
i
2019.07 | 5.1 | F.01U.172.982
Press the "Test" key and then zone key 3.
3
This takes you to the Dis/Enable submenu.
Press zone key 4.
This takes you to the All submenu.
Upon confirmation via the ACK key, all zones, relays
and notification appliances will be disabled/re-
enabled.
5-View Config
6-System Config
1-Date/Time
2-Keypad Tone
3-Language
- 1- A–L
- 2- M–Z
Press the "Menu" key and then zone key 5.
5
This takes you to the View Config submenu.