Technical Data Table - Ferroli ATLAS D ECO 56 UNIT Instructions For Use, Installation And Maintenance

Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 28
ATLAS D ECO 56 UNIT
5.2 Loss of head
Pressure loss water side
60
50
40
30
20
10
0
2000
2500
3000
fig. 36 - Pressure loss
A
mbar
B
Flowrate l/h
3500
4000
4500
5000
cod. 3541Q961 - Rev. 00 - 09/2019

5.3 Technical data table

Data
Number of elements
Max. heating capacity
Min. heating capacity
Max. heat output in heating
Min. heat output in heating
Pmax efficiency (80-60°C)
Efficiency 30%
NOx emissions class
Max. working pressure in heating
Min. working pressure in heating
5500
Max. heating temperature
Heating water content
Protection rating
Power supply voltage
Electrical power input
Empty weight
Combustion chamber length
Combustion chamber diameter
Pressure loss on fume side
Unit
ATLAS D ECO 56 UNIT
no.
5
kW
53.2
(Q)
kW
31.5
(Q)
kW
50
(P)
kW
30
(P)
%
94.0
%
97.3
3
NOx
bar
6
(PMS)
bar
0.8
°C
100
(tmax)
litres
28
IP
X0D
V/Hz
230/50
W
245
kg
232
mm
550
mm
300
mbar
0.38
37
EN

Advertisement

Table of Contents
loading