Prior to servicing, the electrode must be removed from the system.
1. Remove the pH electrode from the line and clean the sensor tip with a clean, non-abrasive cloth.
2. Place the electrode in a buffer solution with a known and accurate pH of 7. Solution must be grounded
by placing temp comp ground probe in solution also.
3. Scroll through the set up menu until you reach the "SYSTEM SET" screen.
4. Press ENTER and use the DOWN arrow to find the "CENTER PH" option. Press ENTER while the
electrode is in the buffer solution.
5. Replace the pH electrode in the line and make any necessary adjustments to the pH reading using
the normal pH calibration procedure.
6. Press the SET UP/RUN key to resume normal operation
VIII. Advantage Controls' Product Warranty
Advantage Controls warrants control systems of its manufacture to be free of defects in material or workmanship.
Liability under this policy extends for 24 months from date of installation. Liability is limited to repair or
replacement of any failed equipment or part proven defective in material or workmanship upon manufacturer's
examination. Removal and installation costs are not included under this warranty. Manufacturer's liability
shall never exceed the selling price of equipment or part in question.
Advantage disclaims all liability for damage caused by its products by improper installation, maintenance,
use or attempts to operate products beyond their intended functionality, intentionally or otherwise, or any
unauthorized repair. Advantage is not responsible for damages, injuries or expense incurred through the use
of its products.
The above warranty is in lieu of other warranties, either expressed or implied. No agent of ours is authorized
to provide any warranty other than the above.
30 Day Billing Memo Policy
Advantage Controls maintains a unique factory exchange program to ensure uninterrupted service with
minimum downtime. If your in warranty controller malfunctions, call 1-800-743-7431, and provide our
technician with Model and Serial Number information. If we are unable to diagnose and solve your problem
over the phone, a fully warranted replacement unit will be shipped, usually within 48 hours, on a 30 Day
Billing Memo.
This service requires a purchase order and the replacement unit will be billed at current list price for that
model less any applicable resale discount. Upon return of your old unit, credit will be issued to your account
if the unit is in warranty. If the unit is out of warranty or the damage not covered, a partial credit will be applied
based upon a prorated replacement price schedule dependent on the age of the unit. Any exchange covers
only the controller or pump. Electrodes, liquid ends and other external accessories are not included.
FCC Warning
This equipment generates and uses radio frequency energy and if not installed and used properly, that is, in
strict accordance with the manufacturer's instruction, may cause interference to radio communications. It has
been type tested and found to comply with the limits for a class A computing device pursuant to subpart J of
part 15 of FCC Rules, which are designed to provide reasonable protection against such interference when
operated in a commercial or industrial environment. Operation of this equipment in a residential area is likely
to cause interference in which case the user, at his own expense, will be required to take whatever measures
necessary to correct the interference.
23

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the MicroTron and is the answer not in the manual?

Table of Contents