Units with selectable feed timer(s) will have this SET
UP menu for selecting the chemical feed method
and setting the feed time. A selectable feed timer
can be programmed to be one of the following:
1. PULSE TIME - A timer activated by dry
contacts from a contacting head water meter
and includes an accumulator for counting the
number of pulse (contacts) before starting the
timer.
2. WITH BLEED - A feed limit timer that runs
during a bleed cycle. The chemical feed will run
for as long as the bleed occurs or until the limit
time is reached.
3. POST BLEED - This timer counts how long
a bleed cycle lasts then runs the chemical
feed after the cycle is over for a user defined
percentage of the bleed time. A limit timer
prevents over feeding.
4. PERCENTAGE - A continuously repeating
timer where the cycle timer can be programmed
along with the percentage of ON time for the
cycle.
6.
BIOCIDE SET
-- CHEM A PULSE TIME --
CHEM PULSES XX
To change # of pulses
ENTER
CHEM A TIMER XX.XX Min.Sec
To change Chem A timer
ENTER
Returns to CHEM FEED SET
-- CHEM A WITH BLEED --
CHEM A LIMIT XX.XX Min.Sec
To change limit
ENTER
Returns to CHEM FEED SET
Shows timer currently selected
ENTER
ENTER
ENTER
To bypass the feed method selection
-- CHEM A POST BLEED --
CHEM A PERCENT XX
ENTER
CHEM A TIMER XX Min.
ENTER
Returns to CHEM FEED SET
-- CHEM A PERCENTAGE --
CHEM PERCENT XX
ENTER
CHEM A CYCLE XX.XX
ENTER
Returns to CHEM FEED SET
14
-- CHEM FEED SET --
To change to a different timer
To cycle through timer options
CHEM A PULSE TIME
CHEM A WITH BLEED
CHEM A POST BLEED
CHEM A PERCENTAGE
To Select timer
To change percentage
To change limit time
To change percentage
To change cycle time