Banner SureCross DX80 Quick Start Manual page 2

Ultrasonic node
Hide thumbs Also See for SureCross DX80:

Advertisement

After entering binding mode, the Node's LED blinks slowly, alternating between red and green. After the Node receives a valid binding
code from the Gateway, the red and green LEDs are both illuminated continuously, resulting in a slightly orange light.
Step 3. The device automatically resets.
Step 4. To identify the device, write the Node address on the Node's label.
Step 5. Repeat this sequence (Node step 3 and Node step 4) for as many Nodes as you need to bind. When using this addressing
system, up to 47 Nodes may be addressed by a single Gateway.
If two Nodes are accidentally assigned the same address, rerun the binding procedure on one of the Nodes to reassign the Node ad-
dress. The binding sequence may be run on a Node as many times as necessary. If a Node is put into binding mode but does not receive
a binding code from a valid Gateway with 60 seconds, the Node automatically exits binding mode.
On the Gateway
Step 1. Single click either button 1 or button 2 on the Gateway to exit binding mode and reboot.
A few seconds after exiting binding mode, the Node's LED blinks green, indicating it is synchronized to the Gateway. The Gateway enters
standard operating mode with the LCD autoscrolling through the menu options.
Optical Commissioning Device
The optical commissioning device is an LED flashlight and is used
to trigger binding between the FlexPower Node and a Gateway.
Model Number: BWA-MGFOB-001
Click and Hold. Click and hold the LED light within one centimeter of the receiving window to wake the FlexPower Node from "deep
sleep." If your Node is not in "deep sleep," clicking and holding the LED light will put it into "deep sleep." While in "deep sleep" mode, the
Node does not attempt to transmit to the Gateway and remains in deep sleep until an LED light at the receiving window wakes it up.
Triple click. Triple clicking at the receiving window puts the Node into binding mode. The Node is assigned the Node address the Gate-
way's rotary dials are set to. Before putting the Node into binding mode, verify the Gateway's rotary dials are set to ensure the Node will
be binding to the correct Node address.
Double click. If the Node is in binding mode, double clicking the LED exits binding mode without binding the Node to the Gateway.
Modbus Register Table
I/O
Modbus Holding Register
Gateway
1
1
1 + (Node# × 16)
2
2
2 + (Node# × 16)
7
7
7 + (Node# × 16)
8
8
8 + (Node# × 16)
14
14
14 + (Node# × 16)
15
15
15 + (Node# × 16)
16
16
16 + (Node# × 16)
The temperature = (Modbus register value) ÷ 20. Temperature values are stored as signed values in the Modbus register. A 0 in the
register is interpreted as 0°; and 65535 in the register (0xFFFF) is interpreted as −1 ÷ 20 = −0.05°.
2
I/O Type
Any Node
Ultrasonic (mm)
Temperature (°C/°F)
Reserved
Device Message
Ultrasonic TEACH
Control Message
Reserved
www.bannerengineering.com - tel: 763-544-3164
I/O Range
Holding Register Representation
Min.
Max.
Min. (Dec.)
0
4000
-1638.3
+1638.4
0
1
SureCross DX80 Ultrasonic Node
Receiving
window
Max. (Dec.)
0
65535
0
65535
0
1
P/N 164800 Rev. A