Specifications - Xtralis ICAM ILS-1 Product Manual

Table of Contents

Advertisement

Xtralis ICAM ILS-1 Product Guide

11 Specifications

Number of Detectors
Filtration
Flow Monitoring
Supply Voltage
Relay Contact Ratings
Maximum Supply Current
Maximum Pipe Length
Environmental Protection
Operating Temperature
Operating Humidity
Approvals
CE Certification
Bargraph Value
Fan Speed
Current (mA)
Note: Typical current consumption figures for different fan speeds. Results are based upon an ILS-1
installation with 10 m of standard, 25 mm aspirating pipe per channel. The unit was powered
from a 24 VDC power supply.
18
Table 11-1: General ILS-1 Specifications
1 or 2, Laser based Analog Addressable
Single stage dust particle filter
Thermal device, high and low thresholds. 10 element bar graph indication.
18 to 30 VDC (24 VDC Nominal)
1 A at 30 VDC
350 mA at 24 VDC with no aspirating pipe. See table below for typical
Currents/Fan Speeds.
100 m + 100 m in Tee Configuration
IP65 with exhaust fitted (IP23 without)
-10 to 50ºC
10 to 95% RH (non-condensing)
EN54-20 by VdS (G206066)
EN61000-6-3:2001(+A11:2004) (EMC)
EN60950-1:2006 (Safety)
CPD (89/106/EEC)
Table 11-2: Typical Current Consumption vs Fan Speed
0
1
2
1
2
3
110
120
130
3
4
5
4
5
6
150
170
190
Xtralis ICAM
6
7
8
7
8
9
220
235
265
www.xtralis.com
9
10
300

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents