4.8.1 Single Pipe Configuration
Figure 4-4: Single pipe configuration for an ILS-1 system
The single pipe configuration can have a maximum length of 100 m with up to 18 x 3 mm sampling
holes and a 6 mm end hole.
4.8.2 Double Pipe Tee Configuration
Figure 4-5: Double pipe tee configuration
The double pipe configuration can have a maximum length of 200 m (100 m per branch) with up to 9 x 3
mm sampling holes and a 6 mm end hole per branch. The distance from the unit to Tee should be at
most 1 m and pipes should be balanced with equal lengths and equal number of holes. See Section 9:
EN54-20 Sensitivity Classes for details for EN54-20 class sensitivity limits.