Page 1
VESDA VLS Product Guide July 2016 Document: 10279_10 Part Number: 19147...
Page 3
You acknowledge that you have not relied on any oral or written information, representation or advice given by or on behalf of Xtralis or its representatives.
Page 4
This manual is written to provide you with comprehensive knowledge of the detector. This manual introduces you to the VESDA VLS features, technical specifications and gives an understanding of its components and their function. You will also find instructions on installing, cabling and powering up the detector.
Page 5
This Xtralis product incorporates a laser device and is classified as a Class 1 laser product that complies with FDA regulations 21 CFR 1040.10. The laser is housed in a sealed detector chamber and contains no serviceable parts.
Page 6
Class C detectors passed EN 54-20 approvals testing with 60 holes and 0.65% obscuration/m detector sensitivity Product Listings ActivFire LPCB VNIIPO EN 54-20 Regional approvals listings and regulatory compliance vary between VESDA product models. Refer to www.xtralis.com for the latest product approvals matrix. Document: 10279_10 Part Number: 19147 www.xtralis.com...
Termination Card Power Source Backup Battery Power Backup battery size calculation sheet Starting Up Installation Checklist 10 Preliminary Systems Check 11 Maintenance 11.1 Replacing the chassis/Air Inlet Pipe Manifold 11.2 Internal Wiring for the VESDA VLS 12 Spare Parts Index www.xtralis.com...
Page 8
VESDA VLS Product Guide VESDA by Xtralis This page is intentionally left blank. www.xtralis.com...
VESDA VLS Product Guide Introduction The VESDA VLS is an aspirating smoke detector providing very early warning of fire conditions by drawing air samples through an air sampling pipe network. The detector chamber can detect presence of smoke at very low concentrations. The embedded and PC software complimenting the VESDA VLS provides a wide range of user defined parameters and reporting capabilities.
Page 10
VESDA VLS Product Guide VESDA by Xtralis This page is intentionally left blank. www.xtralis.com...
An integrated Aspirator draws air in the sampling pipes through a Pipe Inlet Manifold (up to four pipes can be connected to a VESDA VLS detector). For further information on air sampling pipe network, refer to the Pipe Network Design and Installation Manuals.
When smoke is detected at a higher level than the scan threshold, for a period exceeding the configured scan delay (0 to 10 seconds), the detector performs a fast scan. During the fast scan operation the VESDA VLS samples air from each sector (pipe) separately by controlling the scanner valves in the inlet manifold. The fast scan sequence for each pipe is approximately 4 seconds.
Page 13
VESDA by Xtralis VESDA VLS Product Guide 2.1.4 Sector Factor By setting appropriate sector factors it is possible to set different alarm thresholds for each of the four sectors. The detector uses the sector factor to automatically calculate the alarm thresholds appropriate for each sector based on the configured alarm thresholds.
One or more devices can be integrated with the VESDA VLS detector. These are normally configured at the factory prior to shipping, but can also be installed at a later time. The standard VESDA VLS comes with 7 relays or in an optional 12 relay version. The modules that can be integrated are:...
Page 15
Display Module The VESDA VLS Display Module is mounted either on the detector front cover or at a remote location in a remote mounting box or a 19" subrack. It provides a visual representation of the smoke levels and the four alarm stages for the assigned detector.
Page 16
VESDA VLS Product Guide VESDA by Xtralis Table 2-1: Remote Display Module (continued...) Threshold Indicators The illuminated LEDs represent visual settings for ALERT, ACTION, and FIRE 1 alarm levels. The FIRE 1 indicator is always at the top. Fault LEDs The Fault LEDs illuminate to indicate:...
Page 17
VESDA VLS immediately after a fast scan mode if a fire condition is generated Figure 2-4: The Display Module when the VESDA VLS is in a scan mode and immediately after the scan mode has been completed 2.2.3 LCD Programmer The LCD Programmer is used for configuring, commissioning and maintenance of the devices on VESDAnet.
VESDA VLS Product Guide VESDA by Xtralis VESDA VLS Components Legend A Front Cover Pipe Inlet Manifold B Termination Card Air Filter C Blank Card Protecting Processor Card G Aspirator D Chassis with Laser Detector Chamber H Mounting Box/Enclosure Figure 2-6: An exploded view of the detector...
Weight 4.0 kg (9 lbs) including Display and Programmer Modules Operating Conditions Temperature: (To operate the VESDA VLS Tested to: -10°C to 55°C (14°F to 131°F) Detector Ambient: 0°C to 39°C (32° to 103°F) detector outside these parameters Sampled Air: -20° to 60° C (-4° to 140° F)
Page 20
VESDA VLS Product Guide VESDA by Xtralis Table 3-1: Product Specifications (continued...) Specification Value IP Rating IP30 Cable Access 8 x 25 mm (1in) knockouts in various positions Cable Termination Screw terminal blocks (0.2-2.5 sq mm, 30-12 AWG) Sensitivity Range 0.005 to 20% obs/m (0.0015 to 6.25% obs/ft.) Threshold Setting Range Alert: 0.005 - 1.990% obs/m...
VESDA VLS Product Guide VESDA by Xtralis Relays The relays on the Head Termination card interface to Fire Alarm Control Panels communicating faults, alarms and isolate states. The relays can be programmed using PC based software or the LCD Programmer and can be assigned multiple assignments.
Page 26
VESDA VLS Product Guide VESDA by Xtralis 3.4.4 General Purpose Input (GPI) Functions The input terminal requires a voltage supply between 5V and 30 VDC to operate. The input is isolated from the system by an opto-coupler device. Connect the GPI + terminal to the positive output and the GPI - terminal to the ground output of the external device.
VESDA VLS Product Guide Mounting the Detector The VESDA VLS can be mounted onto the wall or on any suitable secure surface using the mounting bracket. It is strongly recommended that the detector is mounted on to the mounting bracket included with the packaging.
VESDA VLS Product Guide VESDA by Xtralis Mounting the Detector in the Inverted Orientation If the detector is fitted with a LCD Programmer and/or a Display Module, reorient these to the inverted position. Mount the detector in inverted orientation onto the mounting bracket.
VESDA by Xtralis VESDA VLS Product Guide Recess mounting kit These kits are used to house a detector inside a wall cavity. Figure 4-4: Recess mounting kit www.xtralis.com...
Page 30
VESDA VLS Product Guide VESDA by Xtralis This page is intentionally left blank. www.xtralis.com...
VESDA by Xtralis VESDA VLS Product Guide Connecting to the Pipe Network Inlet Pipes The inlets in the pipe inlet manifold are designed to receive a standard pipe of 25 mm (1 in) OD. A 25 mm to 1.050 inches adaptor to fit the pipe inlet manifold is included for all shipments to USA.
VESDA VLS Product Guide VESDA by Xtralis Managing the Exhaust Air To exhaust air from the detector, use the exhaust ports at the rear or at the bottom of the head mounting box. Remove the appropriate exhaust port plugs and if required, connect an outlet pipe to the exhaust manifold. In the event the side port is used as an air exhaust port, press out the knockout hole.
Wiring Connections Termination Card The termination card acts as the interface for VESDAnet, power supply, relays and the General Purpose Input (GPI). The VESDA VLS is available with a 7 or a 12 Relay termination card. Legend VESDAnet terminals Power terminals...
Page 34
RS 485 (Belden 9841 - 120 Ohm) twisted pair cables, or similar cables be used. The VESDA VLS is shipped with the VESDAnet A and B terminals looped. If the detector is not to be networked with other devices, then do not disturb this loop. Remove this loop to connect the detector to the VESDAnet.
Page 35
VESDA by Xtralis VESDA VLS Product Guide 6.1.3 Typical Wiring To Fire Alarm Control Panel (FACP) The diagram below shows the correct way to wire VESDA detectors to a conventional fire alarm control panel (FACP). It also shows where an End Of Line (EOL) resistor is correctly installed.
Page 36
VESDA VLS Product Guide VESDA by Xtralis This page is intentionally left blank. www.xtralis.com...
The detector has reverse polarity protection to minimize the risk of reverse power connection to the detector. Notes: Regional differences in power supply may impact on power connection. Please contact Xtralis technical support for more information. Operating the detector when DC supply voltage is outside the voltage range of 18 VDC and 30 VDC may cause damage to the device.
Page 38
VESDA VLS Product Guide VESDA by Xtralis This page is intentionally left blank. www.xtralis.com...
Backup Battery Power The power supply for the VESDA VLS is switched to a back up battery in the event of a mains power supply disruption. The size of the back up battery is determined by local standards and codes, the total power required by the system, back up time required, allowance for reduction in capacity with age and expected temperature variations.
Page 40
VESDA VLS Product Guide VESDA by Xtralis This page is intentionally left blank. www.xtralis.com...
VESDA VLS Product Guide Starting Up After installing the VESDA VLS detector it is necessary to power up the system: The system takes approximately 15 seconds to power up If the system fails to power up, check all power wires are secured to its terminals and the polarities of the...
VESDA VLS Product Guide VESDA by Xtralis Installation Checklist Site Name Address Detector Serial Number(s) and Date of Manufacture Name of Installer Signature Date Perform the following checks listed below to ensure that all the necessary items are completed before handing over to a commissioning engineer.
A preliminary systems check is required after installing the VESDA VLS detector, before it is commissioned for use. The check can be conducted by connecting the detector to a LCD Programmer or using Xtralis VSC PC based software. The preliminary systems check includes:...
Page 44
VESDA VLS Product Guide VESDA by Xtralis This page is intentionally left blank. www.xtralis.com...
Maintenance can be conducted by the original installer, VESDA distributor or an approved service contractor. To work effectively the VESDA VLS detector needs to be supported by a well designed Pipe Network. The Maintenance Schedule includes the maintenance required for the Pipe Network. Given below is a suggested Maintenance Schedule for the VESDA VLS detector.
1. Isolate the VESDA VLS by pressing the Isolate button or by selecting Isolate Zone from the Zone menu in Xtralis VSC. This isolates the outputs from the unit to a fire alarm panel and other third party devices such as building management systems.
Page 47
12. Attach the replacement manifold and chassis by reversing the procedure above. 13. Configure the VESDA VLS using Xtralis VSC by highlighting the detector in the Device Tree Window and selecting Restore Node Configuration from the Device Menu, or reprogram the detector manually...
VESDA VLS Product Guide VESDA by Xtralis 11.2 Internal Wiring for the VESDA VLS The table below provides the cable loom interconnecting details inside the detector. Use the look up table in conjunction with the attached circuit diagram to assist with maintenance.
Page 49
VESDA by Xtralis VESDA VLS Product Guide Legend A Detector chamber Processor card B Programmer module Aspirator C Display module G Flow sensor card D Detector terminal card Figure 11-5: Internal wiring diagram www.xtralis.com...
Page 50
VESDA VLS Product Guide VESDA by Xtralis This page is intentionally left blank. www.xtralis.com...
Need help?
Do you have a question about the VESDA VLS and is the answer not in the manual?
Questions and answers