Page 1
Dir. 2006/42/EC:MD (annexe ll, sub B) Please read this document carefully prior to commencing building into an air handler Subject to modifications Reznor Europe N.V. – J.& M. Sabbestraat 130 – B 8930 Menen Tel +32 56 529 511 – fax +32 56 529 533...
Page 2
(Directive 2006/42/EC (annex ll, Sub B) PROHIBITION TO PUT INTO SERVICE Reznor Europe N.V. J & M Sabbestraat 130 B 8930 Menen Belgium Herewith declares that: Power-vented gas-fired air heaters, type: RHC 8000 RJL DJL series Models 8050 06 8030 06 8125M.15 8075-09 8045 09 8150M.18...
Page 3
INDEX ......................2 ECLARATION STATEMENT ........................4 EFINITIONS .......................4 ASIC INFORMATION ....................9 RACTICAL APPLICATION ....................10 IMITATIONS FOR USE & ..................12 URNER CONTROLS SECTION ......................13 AS CONNECTION ....................14 LECTRICAL EQUIPMENT 8000(M) ...............14 OMBUSTION CIRCUIT RHC 8000(M) ...............17 OMBUSTION CIRCUIT RHC ..................20 RESSURE DROP INFORMATION ..............23 EATING SECTION WITH BY PASS CHANNELS...
1.0 D EFINITIONS ASIC INFORMATION Jacket-less: instructions contained this A gas-fired air heater supplied as a skeleton document apply to the models RHC appliance e.g. without case or cover. 8000(M) RJL/DJL gas fired fan assisted warm air heaters. Module: The jacket-less gas-fired air heater. Models RHC 8000(M) RJL are intended for use in appliances as outdoors (roof Constructor:...
Page 8
Figure 3b: Back side view RHC 8125M, 8150M &8175M DJL/RJL (n° 59710_03) Figure 3c: Back side view RHC 8200M DJL/RJL (n° 59706_03) Dimensions applicable to model RHC 8000M (see fig. 1b/1c –2b/2c & 3b/3c) RHC 8000 M DJL/RJL Type 8125M.15 1272 1089 8150M.18...
Weights (kg) ( table 1) Type 8030 06 8045 09 8050 06 8060 12 8075 09 8075 15 8090 18 8100 12 Unit Packaging Total Type 8125M.15 8150M.18 8175M.21 8200M.24 Unit Packaging Total RACTICAL PPLICATION Figure 4 : Compartment dimensions For horizontal airflow Heat exchanger compartment size.
Page 10
Figure 5 : Installation possibilities for RHC 8000(M) air heater modules Always ensure that the inlet perforated profile plate (when required) is installed at the air ‘inlet’ side of the heat exchanger as shown in figure 5 4.0 L IMITATIONS FOR Heat exchanger compartment 4.1.1 Minimum airflow requirement through heat exchanger enclosure : RHC 8000(M) RJL &...
Page 11
Maximum airflow through heat exchanger 4.1.2 Table 3 indicates the heat output (kW) of the enclosure different models. Special attention must be given to ensure that the temperature rise of the air, The maximum allowable airflow [through the passing through the enclosure around the enclosure (duct channel) around the tubes] can heat exchanger tubes, is high enough to be calculated as follows :...
Page 12
Part or the whole of the tubes may Warning become damaged or can be the source of Use of RHC 8000(M) heating modules poor combustion if the air velocity as for purposes other than those described recommended above is not applied. above could result in severe personal injury or death and cause property damage.
CAUTION : ONNECTION Alterations to the burner and/or its controls, any ¾” or R 1 ¼”) other electrical apparatus supplied as part of the heating module or changing of the settings as supplied is strictly forbidden. To do so is in Attention : All RHC 8000M units are designed contravention of the E.C.
LECTRICAL QUIPMENT OMBUSTION SYSTEM 8000( ‘ ’ OUTDOOR Warning : Ensure that when installing electrical wiring or cables no contact is made with the 8.1.1 Inlets for combustion air and flue outlets burner, heat exchanger or flue arrangement. shall be so designed so that when an Cables or wires must be securely fixed so that appliance finally...
Page 15
Ensure the combustion inlet grill at the The 90° elbow, sealing ring, terminal and the control door panel is completely sealed to combustion air inlet protection grill must be prevent ingress of water. installed according to figure 7. It is forbidden to use the combustion inlet All sealings must be correctly placed in the grill as passage for cables or gas tubes to avoid flowing back of combustion...
Page 16
Figure 8 ASSURE THE SEALING OF THE COMBUSTION AIR INLET GRILL TO THE CONTROLS COMPARTMENT SIDE PANEL IS WATERTIGHT (n° 59008_03) Figure 9: Controls compartment (side) panel for RHC 8000(M) RJL units HOLE (∅112mm or ∅142mm) REQUIRED TO RECEIVE SEALRING (PN 06 22786 104 or 06 22786 134) OPENING REQUIRED TO FIT COMBUSTION AIR INLET GRILL...
Page 17
8.1.3 The terminal outlet (PN 60 50712 300) of thick OMBUSTION SYSTEM wall aluminium pipe supplied must be fitted in RHC 8000(M) DJL ‘INDOOR’ a horizontal plane and be placed so as to fit exactly between the elbow on the combustion fan and the outlet terminal hole with sealing 9.1.1 The DJL Modules are provided with flue...
Page 18
Table 6 : 9.1.4 The combustion air inlet duct must not pass Centre distances combustion air inlet flue through the cabinet panel by more than 50 outlet Model Centre Cabinet hole Connection Ø distance B size 9.1.5 When the DJL model is to be used as a type (mm) (mm) required for...
Page 19
Figure 11a : Combustion air inlet - outlet dimension requirements Combustion air inlet pipe Flue outlet pipe Teflon sealing ring 90° bend Gas passage grommet vinly Rc ¾” or Rc 1 ¼”(PN 06 22783 125 or 06 22783 054) Not delivered with the unit (n°...
Page 20
10.0 P RESSURE LOSS THROUGH HEATING MODULE 10.1 The charts below indicate the pressure exchanger enclosure (see fig. 4 and table drop over the heating module versus the flow volume through heat 10.2 The temperature rise ( T) shown is for 100% heat output.
Page 21
Figure 12c : Pressure losses through RHC8000M. module RHC8175M.21 RHC8200M.24 20100 m³/h 23300 m³/h 21500 m³/h 24000 m³/h 16000 20000 24000 28000 32000 36000 40000 44000 48000 52000 Airflow (m³/h) through the heat exchanger enclosure ΔT ΔT Figure 12d : Pressure loss through a single RHC8000 module RHC8075-15 RHC8090-18...
Page 22
Figure 12e : Pressure losses through a RHC8000M. module RHC8125M.15 RHC8150M.18 18200 m³/h 15600 m³/h 18000 m³/h 21000 m³/h 14000 16000 18000 20000 22000 24000 26000 28000 30000 32000 34000 36000 38000 40000 Airflow (m³/h) through the heat exchanger enclosure ΔT 24 23 22 21 ΔT...
Page 23
11.0 H A) The by-pass can either be mounted on top of the EATING SECTION WITH BY PASS heat exchanger or besides the heat exchanger as CHANNEL in figure 13 shown The recommended maximum by-pass dimensions for a given air flow (V ) can be calculated as 11.1 By-pass requirements...
Page 24
As explained above, the air flow V through Note In this case 2. m³/s flows through the heat exchanger enclosure must be used in (= 10750m³/h) the heat exchanger enclosure. figure 12 to extract the correct total pressure The remaining 2. m³/s flows through drop over the RHC module with by-pass.
Page 25
Figure 13a : FRONT VIEW Figure 13b : SIDE VIEW 0710RHC8-JLNLEN 25/36...
Page 26
12.0 I Table 8a NSTALLATION OF UNITS IN Minimum airflow requirements for 2 RHC SERIES units in series : Model 12.1 General (m ³ /h) (m ³ /h) 2x 8030 06 3750 4400 12.1.1 Two or three RHC units can be installed in 2x 8045 09 5650 6600...
Page 27
Pressure drop for 2 units in series Figure 14a Pressure losses through 2 RHC8000 heating modules in serie 2x RHC8050-06 2x RHC8075-09 2x RHC8100-12 12400 m³/h 9300 m³/h 6200 m³/h 14300 m³/h 10790 m³/h 7150 m³/h 5000 7000 9000 11000 13000 15000 17000...
Page 28
Figure 14c Pressure losses through 2 RHC 8000 heating modules in series 2x RHC8075-15 2x RHC8090-18 11200 m³/h 9300 m³/h 14300 m³/h 11900 m³/h 8000 10000 12000 14000 16000 18000 20000 22000 24000 Airflow (m³/h) through the heat exchanger enclosure ΔT 2x RHC8075-15 ΔT 2x RHC8090-18 Figure 14d...
Page 29
Figure 14e Pressure losses through 2 RHC8000M in series 2x RHC8175M.21 2x RHC8200M.24 23300 m³/h 20100 m³/h 21500 m³/h 24000 m³/h 16000 20000 24000 28000 32000 36000 40000 44000 48000 52000 Airflow (m³/h) through the heat exchanger enclosure 50 47 44 42 40 38 36 32 31 30 29 28 27 26 ΔT 2x ΔT 2x RHC8200M.24...
Page 32
12.4 Multiple heating sections in series with by-pass channels (not applicable for RHC 8000M models) 12.4.1 By-pass requirements : b) By-pass on top of heat exchanger : * Referring to section 4.1.3, a by-pass duct parallel with heat exchanger Model dim.
Page 33
Figure 15 : Installation of air fan 12.4.3 Calculation of alternative by-pass dimension: Due to space restrictions it may not be possible to use the above mentioned maximum dimension by-pass. In this case a smaller by-pass can be applied. Obviously, this smaller by-pass will result in a higher portion of the total airflow through the heat exchanger enclosure and consequently in a higher total pressure drop...
14.0 NSTALLATION OF MULTIPLE RHC…. DJL UNITS WITH VERTICAL not applicable for FLUE OUTLET RHC 8000M models * unit 4 : proceed as follow (see drw 3): Install on the collar of the combustion 14.1 Attention : remove the 90° elbow (mounted on ventilator outlet a 45°...
Need help?
Do you have a question about the RHC 8000 RJL and is the answer not in the manual?
Questions and answers