Start-Up, Calibration And Operation Of The Burner; Notes On Safety For The First Start-Up; Burner Calibration; Adjusting The Nozzle Flow Rate - Riello RL 70/E Installation, Use And Maintenance Instructions

Light oil burner
Table of Contents

Advertisement

5

Start-up, calibration and operation of the burner

5.1

Notes on safety for the first start-up

The first start-up of the burner must be carried out
by qualified personnel, as indicated in this manual
and in compliance with the standards and regula-
WARNING
tions of the laws in force.
5.2

Burner calibration

The optimum calibration of the burner requires an analysis of the
flue gases at the boiler outlet.
5.3

Adjusting the nozzle flow rate

The nozzle flow rate varies according to the fuel pressure on the
nozzle return.
Diagram (Fig. 33) indicates this relationship for type A4 return flow
nozzles with pump delivery pressure of 290 PSI.
Diagrams (Fig. 33):
Horizontal axis
: PSI, nozzle return pressure
Vertical axis
: GPH, nozzle flow rate
The values indicated in the right side of the diagram, refer to the
data printed on the nozzle.
NOTE:
with a pump delivery pressure of 290 PSI, the pressure on the
nozzle return must not exceed 246.5 PSI.
The pressure difference between pump delivery and nozzle return
must be at least 43.5 PSI. With smaller pressure differences, the
pressure on the nozzle return can be unstable.
5.3.1

Pressure controller

1 - Gauge for pressure in return line
2 - Oil pressure switch
3 - Ring for piston stop
4 - Nut and lock-nut for piston setting
5 - Eccentric adjusting screw
6 - Variable eccentric
7 - Eccentric locking screws
The nozzle return pressure value is indicated by the pressure
gauge 1)(Fig. 34).
The output and the pressure of the nozzle are at maximum when
the servomotor is positioned on maximum.
The fine adjustment of the pressure in the return line may be car-
ried out by changing the setting of the eccentric 6)(Fig. 34), of the
nut and lock-nut 4)(Fig. 34).
20045163
Start-up, calibration and operation of the burner
26
Check the correct working of the adjustment, com-
mand and safety devices.
WARNING
The following settings that have already been made do not require
modification under normal circumstances:
– combustion head;
– servomotor
Type A4 return flow nozzle (45°)
D2355
D1227
GB
Delivery pressure 290 PSI
Return pressure
Fig. 33
Fig. 34

Advertisement

Table of Contents
loading

This manual is also suitable for:

20045065

Table of Contents