Nozzle Installation; Choice Of Nozzle; Recommended Nozzles; Nozzle Assembly - Riello RL 70/E Installation, Use And Maintenance Instructions

Light oil burner
Table of Contents

Advertisement

4.7

Nozzle installation

The burner complies with the emission requirements of the UL 296
Standard.
In order to guarantee that emissions do not vary, recommended
and/or alternative nozzles specified by the manufacturer in the In-
struction and warning booklet should be used.
It is advisable to replace nozzles every year during
regular maintenance operations.
WARNING
The use of nozzles other than those specified by the
manufacturer and inadequate regular maintenance
may result into emission limits non-conforming to
the values set forth by the regulations in force, and
in extremely serious cases, into potential hazards to
people and objects.
CAUTION
The manufacturing company shall not be liable for
any such damage arising from nonobservance of
the requirements contained in this manual.
4.7.1

Choice of nozzle

See diagrams (Fig. 33 page 26).
In case an intermediate delivery between the two values indicated
in the diagrams (Fig. 33 page 26) is required, a nozzle with higher
delivery must be chosen. Delivery reduction will be obtained by
means of the pressure regulator.
4.7.2

Recommended nozzles

Type A4 return flow nozzles - 45° angle.
4.7.3

Nozzle assembly

At this stage of installation the burner is still disassembled from the
blast tube; it is therefore possible to fit the nozzle with the box
wrench 1)(Fig. 14), inserting the wrench through the central hole in
the flame stability disk.
Do not use any sealing products such as gaskets,
sealing compound, or tape. Be careful to avoid
damaging the nozzle sealing seat.
WARNING
Finally remount the burner 3)(Fig. 15) on the slide bars 2) and slide
it up to the flange 5), keeping it slightly raised to prevent the flame
stability disk from pressing against the blast tube.
Tighten the screws 1) on the slide bars 2) and screws 4) fixing the
burner to the flange.
4.8

Electrode adjustment

Make sure that the electrodes are positioned as shown in (Fig. 17).
20045163
Installation
If it proves necessary to change a nozzle with the burner already
fitted to the boiler, proceed as outlined below:
– Pull back the burner on its slide bars as shown in
(Fig. 13)page 17.
– Remove the nuts 1)(Fig. 16) and the disk 2).
– Use wrench 3)(Fig. 16) to change the nozzles.
D1220
D1222
18
GB
D2528
Fig. 14
D1221
Fig. 15
Fig. 16
Fig. 17

Advertisement

Table of Contents
loading

This manual is also suitable for:

20045065

Table of Contents