Technical Data - WAGO I/OSYSTEM 750 Series Manual

Fieldbus independent i/o modules, incremental encoder interfaces
Hide thumbs Also See for I/OSYSTEM 750 Series:
Table of Contents

Advertisement

26 •
750-637/000-001 [Inc.Enc./24V/32Bit/Diff.]

Technical Data

Technical Data
Module specific Data
Sensor connection
Current consumption (internal)
Counter
Operation Mode Capture
Operation Mode Preload
Quadrature decoder
Zero impulse latch
Commands
Velocity
Max. operating frequency
Time constant input LATCH
Time constant input GATE
Time constant input REF
Power supply
Current consumption (24 V)
Sensor Operation voltage
Sensor Output current
Internal bit width
Dimensions W x H* x L
* from upper edge of DIN 35 rail
Weight
Digital Outputs (N1, N2)
Output voltage
Output current
Output resistance
Digital Inputs (Latch, Gate, Ref)
Input voltage
Input current
Quadrature Inputs (A, /A, B, /B, C, /C)
Input voltage A, /A
Input voltage B, /B
Input voltage C, /C
max
max.
typ.
typ.
A, /A, B, /B, C, /C (/A, /B, /C are inversed)
110 mA
32 bits binary
32 bits
32 bits
4-fold interpretation
32 bits
read, write, activate
16 Bit (increments per 1ms)
250 kHz
364 µs
32 µs
32 µs
DC 24 V (- 15 % ... + 20 %)
12 mA (without sensor and without load)
DC 5 V
300 mA
1 x 32 bits data
2 x 8 bits control / status
24 mm x 64 mm x 100 mm
ca. 105 g
DC 24 V
0,5 A short-circuit-protected
160 m
(0) DC –3 V ... +5 V
(1) DC +15 V ... +30 V
Latch: 5 mA
Gate and Ref: 7 mA
(0) DC -30 V < (U(A) - U(/A)) < DC -15 V
(1) DC +30 V > (U(A) - U(/A)) > DC +15 V
(0) DC -30 V < (U(B) - U(/B)) < DC -15 V
(1) DC +30 V > (U(B) - U(/B)) > DC +15 V
(0) DC -30 V < (U(C) - U(/C)) < DC -15 V
(1) DC +30 V > (U(C) - U(/C)) > DC +15 V
WAGO-I/O-SYSTEM 750
I/O Modules

Advertisement

Table of Contents
loading

This manual is also suitable for:

750-637750-637/000-001750-637/000-002750-637/000-004

Table of Contents