GASKET OVERLAPPED AND PLACED
OVER BASERAILS AND FRAME JOIN
OUTLET SIDE ONLY
GASKET APPLIED TO OUTLET SIDE
OF OUTDOOR UNIT SPLIT ONLY

RIGGING AND STACKING

The ERV section sizes 03-14 are shipped stacked (fully assem-
bled) and size 17 with 4, 6, or 8 in. baserails are shipped
stacked (fully assembled). These units can be stacked and un-
stacked, as required, during installation by following the same
procedure as for larger units described below.
The ERV section sizes 17 with 10 in. baserails and sizes 21-61
are shipped unstacked due to shipping height limitations. The
lower sections are all assembled on baserails and shipped sepa-
rately. The upper sections are also assembled on baserails and
shipped separately. Rigging and setting the lower sections is
the same as for a standard 39MN indoor or 39MW outdoor
base unit. Refer to the Rigging Information label on the unit.
For sizes 36-61, the ERV wheel bypass sections are shipped
stacked. upper section must be removed from lower section before
installation.
CAUTION
The upper sections MUST be rigged and lifted one at a time
or injury or unit damage may occur.
Rigging and lifting upper sections:
1.
Use all lifting brackets provided on the baserail section.
2.
Lift and carefully set the section on top of the lower sec-
tions using guide pins to align and avoid damage to gasket.
For sizes 21-30, upper sections should be stacked onto the
lower sections starting with the section upstream and
downstream of the wheel section, and then moving out-
ward to each end of the unit.
Repeat this process for the remaining ERV sections.
Fig. 163 — Gasket Installation
For sizes 36-61:
1.
Connect lower ERV return air module sections to the main
unit. Make standard connections with hardware at base rails,
intelliclamps, and top frame brackets. See Fig. 164.
2.
Remove screws securing the lower panel to the frame rail on
the outlet wall supply air module. Save screws and panel for
reinstallation. See. Fig. 165.
3.
Verify gasket is present and secure at base rail tab to roof cap
connection.
192
93M6X70500X000002, (¾" x 2" GASKET)
SHALL BE INSTALLED ON THE OUTLET
FRAME/BASERAIL LOOPS OF THE
FOLLOWING SECTIONS:
LAST SECTION OF OUTDOOR AIR MODULE
LAST SECTION OF EXHAUST AIR MODULE
ERV MODULE Y1/Y2/Y3
MAIN UNIT
Fig. 164 — Connect Lower ERV
Return Air Module Section
ERV RETURN
AIR MODULE